RM Series 100~1200kVA Intelligent Modular UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

The RM series UPS uninterruptible power supply adopts advanced Type I three-level technology, realizing comprehensive redundant design from modules to the whole machine. Single cabinet one megawatt, easy to expand, easy to upgrade, 1.2MW single cabinet occupies only 1.32m². Online double conversion mode efficiency up to 97%, super ECO mode efficiency up to 99%, intelligent sleep, high efficiency at low load, green and low carbon, providing safe, efficient and reliable power supply for critical loads in large and super-large data centers.

Power range: 100~1200kVA.

Operating mode: three-in three-out, double conversion online operation.

Widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Performance features include: high efficiency and energy saving, on-demand capacity expansion, intelligent operation and maintenance, safe and reliable.

Product Parameters
Model RM600/100D RM800/100D RM1000/100D RM1200/100D RM1200/100D-F
RM800/100D-F RM1000/100D-F RM1200/100D-S
Capacity 600kVA 800kVA 1000kVA 1200kVA 1200kVA
Main Road Input Input Mode 3P+N+PE
Input Voltage 380/400/415VAC (line voltage)
Power Factor >0.99
Current Distortion Rate THDi<3% (100% linear load)
Voltage Range 323~478VAC (line voltage) full load, 323~380VAC (line voltage), load linearly derated from 100% to 30%
Frequency Range 40~70Hz
Battery Battery Voltage ±240VDC (rated 40 cells), 30 cells derated to 70%, 32-34 cells derated to 80%, 36-38 cells derated to 90%, 40-50 cells no derating
Charging Power 15% * output power (maximum)
Charging Voltage Accuracy 0.01
Bypass Rated Voltage 380/400/415VAC (line voltage)
Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Output Rated Output Voltage 380/400/415VAC (line voltage)
Rated Frequency 50/60Hz
Output Power Factor 1
Output Total Harmonic Distortion (THDu) <1% (linear load), <5% (non-linear load)
Inverter Overload <110%, transfer to bypass after 1 hour; 110%~125%, transfer to bypass after 10 minutes; 125%~150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200ms
System Main Road Mode ≥97%
Noise (1 meter) 75dB@100% load, 70dB@45% load
Operating Temperature 0~40°C
Relative Humidity 0-95% (non-condensing)
Altitude <1000m no derating, between 1000~2000 meters, power derated by 1% for every 100 meters increase
Communication Interface Standard: RS485, USB, CAN, programmable dry contact card, 2 intelligent card slots, 1 expandable dry contact card slot
Options SNMP card, intelligent AS400 card, parallel components, lightning protection components, main bypass same source components, LBS, SMS alarm, RS485 extension card
Dimensions (W*D*H) mm Host 1000*1100*2000 1200*1100*2000 1200*1100*2000 1200*1100*2100 2000*1100*2000
1800*1100*2000 1800*1100*2000
Module 440*795*174, PM100D
Weight (kg) Cabinet 400 590 620 657 760
890 940 1150
Module 53.5