RM Series 25~200kVA Rack-mounted Modular UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Power Range

25~200kVA

Operating Mode

Three-in three-out, double conversion online operation.

Application Fields

Widely used in IDC data centers, network servers and workstations, control systems, communication systems, office environment applications and other fields.

Performance Features

The RM series rack-mounted modular UPS is an online double conversion UPS product with hot-swappable and highly scalable features. The system capacity is 25~200kVA, which is an ideal choice for modern data centers. This series adopts advanced IGBT three-level conversion and dual DSP control technology, with extremely high usability and reliability.

  • High power density: 25kVA module, 2U height, greatly saving floor space and easy expansion.
  • Rack-mounted modular design: The module is compatible with 19-inch standard racks, very convenient for computer room installation.
  • Supported installation methods: rack-mounted installation (recommended to use standard 19-inch cabinets with depth of 1200mm or more), tower installation.
  • Battery cold start: It can be started by battery without mains power.
  • Friendly human-machine interface: 7-inch large color LCD screen (touch screen), rich in information.
  • High input power factor.

 

Product Parameters
Model RM150/25C RM200/25C
Capacity 150kVA 200kVA
Main Road Input Input Wiring 3-phase + N wire + ground wire
Input Voltage 380/400/415VAC (line voltage)
Power Factor >0.99
Current Distortion Rate THDi<3% (100% linear load)
Voltage Range 304~485VAC (line voltage) full load, 304~138VAC (line voltage), load linearly derated from 100% to 40%
Frequency Range 40-70Hz
Battery Battery Voltage ±240VDC (30~50 cells)
Charging Power 20% * active power (maximum)
Bypass Bypass Voltage 380/400/415VAC (line voltage)
Bypass Frequency Range 50/60Hz, settable: ±1Hz, ±3Hz, ±5Hz
Output Rated Output Voltage 380/400/415VAC (line voltage)
Rated Frequency 50/60Hz
Output Power Factor 1
Output Total Harmonic Distortion (THDu) <1% (linear load), <6% (non-linear load)
Inverter Overload 110%, transfer to bypass after 1 hour; 125%, transfer to bypass after 10 minutes; 150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200ms
System Main Road Mode Efficiency ≥96%
Communication Interface RS232, RS485, dry contact, battery cold start
Operating Temperature 0-40°C
Storage Temperature -40°C~70°C
Relative Humidity 0-95% (non-condensing)
Noise (dB) 65dB@100% load, 62dB@45% load
Options SNMP network communication card, parallel components, lightning protection components, 150K machine optional power distribution unit
Cabinet Type 6-module cabinet 8-module cabinet
Dimensions (W*D*H) mm Host 482*916*931 482*916*1550
Host (placed in server cabinet) 482*916*840 (19U) (top entry)
482*916*1368 (31U) (bottom entry, without removing casters)
482*916*1550 (35U) (without removing casters)
  PM25C Module 436*677*85 (2U)
Weight (kg) Host (including modules) 221 (top entry)
254 (bottom entry, without removing casters)
317
PM25C Module 20.5