RM Series 10~90kVA Rack-mounted Modular UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Power Range

10~90kVA

Operating Mode

Three-in three-out / three-in single-out / single-in single-out (RM020/10X, RM040/10X, RM060/10X), double conversion online operation. Three-in three-out (RM030/15X, RM045/15X, RM090/15X), double conversion online operation.

Performance Features

  • Embedded standard cabinet installation: Supported installation methods: rack-mounted installation (recommended to use standard 19-inch cabinets with depth of 1100mm or more), tower installation.
  • Rich supporting products: PDU unit, external bypass unit, integrated battery cabinet (can accommodate 2 groups of 12AH 12V), etc.
  • Ultra-large color LCD touch screen: The host is equipped with a 7-inch LCD touch display, color graphic display, easy operation, and friendly human-machine communication.
  • Quick installation, flexible and convenient: The design elements of rack-mounted modular units greatly meet the flexibility, easy installation, space saving, and easy maintenance required by today's small and medium-sized data centers.
  • Flexible input and output modes: Supports input and output modes: three-in three-out / three-in single-out / single-in single-out.

Application Fields

Widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Product Parameters
Model RM020/10X RM040/10X RM060/10X RM030/15X RM045/15X RM090/15X
Capacity 20kVA 40kVA 60kVA 30kVA 45kVA 90kVA
Main Road Input Input Wiring 3-phase + N wire + PE
Input Voltage 380/400/415VAC (line voltage) 220/230/240VAC (phase voltage)
Current Distortion Rate THDi<3% (100% linear load)
Voltage Range 304~485VAC (line voltage) full load, 304~388VAC (line voltage), load linearly derated from 100% to 40%
Frequency Range 40-70Hz
Battery Battery Voltage ±240VDC (30~50 cells)
Charging Power 20% * active power
Bypass Bypass Voltage 380/400/415VAC (line voltage) 220/230/240VAC (phase voltage)
Overload Capacity 125%, long-term operation; 130%, shutdown after 10 minutes; 150%, shutdown after 1 minute; 150%<load, shutdown after 300 milliseconds 110%, long-term operation; 130%, shutdown after 10 minutes; 150%, shutdown after 1 minute; 150%<load, shutdown after 300 milliseconds
Output Rated Output Voltage 380/400/415VAC (line voltage); 220/230/240VAC (phase voltage)
Rated Frequency 50/60Hz
Output Power Factor 1
Output Total Harmonic Distortion (THDu) <1% (linear load), <5.5% (non-linear load)
Inverter Overload 102%, long-term operation; 110%, transfer to bypass after 1 hour; 125%, transfer to bypass after 10 minutes; 150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200 milliseconds
System System Efficiency Main road mode ≥95%; economy mode ≥98%; battery mode ≥94.5%
Communication Interface RS232, RS485, dry contact, SNMP card (optional), emergency shutdown
Wiring Method Rear entry and bottom entry optional Bottom entry Rear entry and bottom entry optional Bottom entry
Operating Environment 0~40°C (operating temperature); -25°C~70°C (storage temperature); 0~95% (non-condensing)
Noise (dB) (1 meter) <56dB
Cabinet Type 2-module cabinet 4-module cabinet 6-module cabinet 2-module cabinet 3-module cabinet 6-module cabinet
Dimensions (W*D*H) mm  Host 485*697*398 485*697*575 485*751*1033 485*697*398 485*751*575 485*751*1033
Host (placed in server cabinet) 485*697*308 (7U) 485*697*485 (11U) 485*751*928 (21U) 485*697*308 (7U) 485*751*485 (11U) 485*751*928 (21U)
Module 436*590*85 mm (2U)
Weight (kg) Host (including modules) 73 113 175 73 119 175
Module 15.3 (PM10X) 15.5 (PM15X)