1.1 The DL series pumps are vertical, single-suction, multistage, segmented centrifugal pumps, designed for conveying clean water and liquids with physical and chemical properties similar to water at temperatures below 80 °C. The DLR hot water pumps are suitable for media with temperatures below 150 °C.
1.2 The pump is vertically mounted, featuring a compact structure, low noise, safe and stable operation, easy installation and maintenance, and a small footprint.
1.3 The multistage multi-outlet centrifugal pump is a new generation product designed and manufactured on the basis of the DL type pump, incorporating user feedback and the relevant requirements of the fire protection specifications of the Ministry of Public Security, and strictly in accordance with the JB/T2809 — 89 standard.
1.4 Application scope:
This type of pump is particularly suitable for water supply and drainage as well as fire-fighting water systems in high-rise and low-rise residential buildings, hospitals, hotels, department stores, office buildings, etc., for long-distance transportation, and for water used in production process circulation. The multi-outlet pump can be used in applications requiring one pump for multiple purposes, thereby saving investment.
1.5 Operating conditions:
① It can convey clean water or non-corrosive media with physical and chemical properties similar to clean water, with a solid insoluble matter volume not exceeding 0.1% of the unit volume. If the medium contains fine particles, please specify at the time of ordering.
② Medium temperature: DL ≤80 °C, DLR ≤150 °C.
③ The maximum working pressure shall not exceed 2.5 MPa, i.e., system pressure = inlet pressure + pressure during closed-valve operation ≤2.5 MPa.
④ The ambient temperature shall be below 40 °C, and the relative humidity shall be below 95%.