Model |
RH233YL/125 |
RH261YL/125 |
|
DC side specifications |
||
|
Cell |
280Ah/3.2V |
314Ah/3.2V |
|
Battery type |
Lithium iron phosphate |
|
|
Rated discharge rate |
≤ 0.5C |
|
|
Rated voltage |
832V |
832V |
|
Operating voltage range |
728V-936v |
728V-936v |
|
Nominal energy |
233kWh |
261kWh |
|
AC side specifications |
||
|
Rated output power |
125kW |
125kW |
|
AC access mode |
Three-phase three-wire/four-wire |
Three-phase three-wire/four-wire |
|
Rated grid-connected voltage |
400Vac |
|
|
Allowable grid voltage range |
15% |
|
|
Rated grid frequency |
50Hz/60Hz |
|
|
Power factor |
0.99 (rated output power) |
|
|
Power factor adjustable range |
-0.99~0.99 |
|
|
Isolation transformer |
None |
|
|
AC current harmonic |
<3% |
|
|
System specifications |
||
|
Dimensions (L × W × H, mm) |
1030 × 1360 × 2350 |
1030 × 1360 × 2235 |
|
Battery compartment cooling method |
Intelligent liquid cooling |
|
|
Cooling mode of electric compartment |
Intelligent air cooling |
|
|
Protection level |
IP54 |
|
|
Anti-corrosion grade |
C3 ※ |
|
|
Operating temperature range (℃) |
-25 ℃ ~ 55 ℃ |
|
|
Relative humidity |
0 ~ 95% (non-condensing) |
|
|
Maximum working altitude (m) |
≤ 3000 |
|
|
Fire protection system |
PACK level detection and perfluorohexanone fire extinguishing, cabinet level aerosol and water fire fighting |
|
|
System communication interface |
RS485/Ethernet |
|

京公网安备 11010802043282号