Integrated Feeder Terminal Unit (FTU)
Negotiable
China
Area B, 5th Floor, Building 6, No. 288, Ningxia Road, Shinan District, Qingdao City, Shandong Province
+86 400-6678-369
Online Contact
Favorite
Product Introduction

Product Introduction:

The Integrated Feeder Terminal Unit (FTU) is equipped with a built-in medium-voltage carrier communication module and features dynamic graphic model verification through characteristic current and judgment algorithms. It is suitable for the main and branch lines of overhead distribution networks, enabling the identification of the topological relationships of the entire line and achieving automatic mapping and verification. It supports encrypted remote data exchange with the distribution automation master station through fiber optics, wireless, and carrier wave communication methods, allowing for dual-channel switching primarily via the wireless public network with medium-voltage carrier as a backup, enhancing the stability of distribution communication.

Product Features:

  1. Communication Blind Spot Compensation, Wireless/Carrier Dual-Channel Switching

Built-in medium-voltage carrier communication module, with the latest generation of medium-voltage carrier communication technology offering a maximum communication rate of 100kbps and point-to-point communication latency of less than 10ms; enables dual-channel switching primarily via the wireless public network with medium-voltage carrier as a backup, improving the stability of distribution communication.

  1. Graphic Model Verification

Through characteristic current and judgment algorithms, it identifies the topological relationships of the entire line, automatically generating and verifying maps, thereby achieving the function of graphic model verification.

Product Parameters

Equipment

Technical parameters

Parameter Value

Integrated Outdoor Voltage Transformer

Model

JDZW-10RC2

Rated voltage

12kV

Rated frequency

50Hz

Rated voltage ratio

10kV/0.22kV/0.1kV

Accuracy class

Level 3/Level 0.5

Rated secondary output

300VA/10VA

Rated capacity

≤ 5000pF

1min power frequency withstand voltage

42kV

Lightning impulse withstand voltage

(Peak)

75kV

Partial discharge

At 14.4kV ≤ 20pC

Protection level

IP67