Operating Environment:
- Ambient Air Temperature: -5°C to +40°C; daily average temperature must not exceed +35°C. If exceeded, derated operation is required based on actual conditions.
- Altitude: 2000m or below.
- Relative Humidity: Not exceeding 50% at maximum temperature of +40°C. Higher relative humidity is allowed at lower temperatures, e.g., when humidity is 90% at +20°C, consider occasional condensation due to temperature variations.
- Installation Tilt: Not exceeding 5°, with the entire cabinet row relatively level (compliant with GBJ232-82 standard).
- The switchgear must be installed in a location free from severe vibration, impact, and conditions that may cause undue corrosion of electrical components.