Intelligent SF₆ Ring Main Unit
Negotiable
China
Room 908, 9th Floor, Building 1, Yard 2, Jinze West Road, Fengtai District, Beijing, 100073, P.R. China
15210760531
+86 18910035135
Online Contact
Favorite
Product Introduction

The intelligent SF₆ ring main unit fully encloses all live parts inside an SF₆ gas-insulated tank with a protection rating of IP67, completely isolating the switching device from external environmental influences and ensuring safe and reliable operation.

Key Features

Fully insulated, fully sealed, maintenance-free

Three-position load switch with interlocking; clear switch position indication and distribution status display for enhanced safety

Programmed design, standardized process control, and modular assembly for consistent quality

Reliable pressure relief channel and arc-fault-resistant design; passed internal arcing test

Optional DTU and other intelligent devices to enable smart distribution network functionality

Multiple configurations available: top or side cable outlet, emergency high-voltage power interface, secondary module, and aviation plug interface

Custom solutions available based on customer requirements

Applicable Standards

GB/T 3906: Alternating-current metal-enclosed switchgear and controlgear for rated voltages 3.6kV to 40.5kV

GB 1984: High-voltage alternating-current circuit-breakers

GB/T 3804: High-voltage alternating-current load switches for rated voltages 3.6kV to 40.5kV

DL/T 593: Common technical requirements for high-voltage switchgear and controlgear standards

GB/T 1985: High-voltage alternating-current disconnectors and earthing switches

Product Parameters

Technical parameters

Parameters

Load switch (C cabinet)

Circuit breaker (V cabinet)

Combined electrical appliance (F)

Isolating/earthing switch

Rated voltage (kV)

12

24

12

24

12

24

12

24

Rated current (A)

630

630

125

630

Arc extinguishing mode

Gas SF6

Vacuum

Gas SF6

Gas SF6

Power frequency withstand voltage (kV)

42

65

42

65

42

65

42

65

Lightning impulse (kV)

75

125

75

125

75

125

75

125

Rated short-circuit breaking current (kA)

/

20/25

/

/

Rated peak withstand current (kA)

50/63

50/63

/

50/63

Arcing time (S)

1

1

1

/

Mechanical life (times)

5,000

10,000(Spring) 30,000(Permanent magnet)

5,000

3,000

Inflation pressure

0.04Mpa(≈0.4bar)

SF6 Annual Leakage Rate

≤ 0.01

Internal combustion arc grade

A(FLR)

Protection level

IP67/IP41/IP54

Applicable environment

High temperature: +60 ℃

Minimum temperature:-40 ℃

Relative humidity: daily average not more than 95%, monthly average not more than 90%

Seismic grade: 8

Altitude: ≤ 2000m