Mechanical transmission and structure |
Total transmission ratio |
36:1 |
|
Indication precision |
Deviation of less than +2.25° at any of the dial position. |
|
|
Limit switches |
Can be set up at scale positions of 8L/R, 10L/R 12L/R, 14L/R 16L/R as request. |
|
|
Reset of drag hands |
Drag hands can return to position of pointer freely, rapidly and completely once getting the signal from controller. |
|
|
Connection |
-Input shaft socket must match the special flexible shaft very well. -J15 connector connected to OLTC is customized and supplied by Huaming. -J9 terminal connector (type TYCO CAT #350783-1) for connecting to the terminal of controller (type TYCO CAT #350720-1) -J12 terminal connector (type TYCO CAT #350782-1) for connecting to the terminal of controller (type TYCO CAT #350735-1) |
|
|
Electric |
Electric reset solenoid |
Be fit for 120V/50Hz or 120V/60Hz, Maximum on time is 1min |
|
Limit switch |
Type OMRON V152-1C 25 (15A, 125VAC) |
|
|
Hipot |
All terminals to the aluminum alloy housing and between terminals, the power frequency withstanding voltage is 1.5kV, 50HZ/1min. |
|