Product Overview
This series of operating mechanisms is mainly suitable for 10kV/24kV SF6 gas and environmentally friendly gas ring main units. The operating mechanism is primarily used for load breaking, circuit isolation, and reliable grounding.
Performance Features
Mechanism lifespan: Load switch ≥5,000 operations; Grounding switch ≥3,000 operations
Voltage levels: AC220V, DC220V, AC110V, DC110V, DC48V, DC24V
Closing/Opening parameters: Closing/opening time ≤6ms at 85%–110% of rated voltage
Closing/Opening speed: Average closing/opening speed 4–8ms
Phase asynchronism: ≤2ms
Operating Environment
Ambient air temperature: Maximum +60°C; Minimum –40°C
Altitude: ≤4,000 m
Seismic intensity: ≤8 degrees
Relative humidity: Daily average ≤95%; Monthly average ≤90%
Installation site: Free from fire, severe pollution, corrosion, or violent vibration