Intelligent Eco-friendly Gas-insulated Ring Main Unit

Negotiable
China
Room 908, 9th Floor, Building 1, Yard 2, Jinze West Road, Fengtai District, Beijing, 100073, P.R. China
15210760531
+86 18910035135
Online Contact
Favorite
Product Introduction

The Intelligent Eco-friendly Gas-insulated Ring Main Unit is a new-generation product independently developed by Beijing HCRT. Based on green environmental design principles, it offers reasonable layout, reliable power supply, compact structure, easy installation, flexible operation, small footprint, and excellent cost-performance. In terms of overall dimensions, it is comparable to conventional SF₆ gas-insulated cabinets and is the preferred replacement for both SF₆ ring main units and solid-insulated ring main units.

Key Features

Insulation medium: dry air, completely SF₆-free, green and environmentally friendly

Fully insulated, fully sealed, micro-positive pressure design; capable of safe operation even at zero gauge pressure

Three-position isolating switch with safe operation and visible break

Compact modular design with flexible configuration options

Vacuum interrupter replaces grounding switch for short-circuit making, ensuring safety and reliability

Multiple configuration options: top or side cable outlet, emergency high-voltage power interface, secondary module, and aviation plug interface

Custom solutions available according to customer requirements

Applicable Standards

GB 1984 High-voltage alternating-current circuit-breakers

GB/T 1985 High-voltage alternating-current disconnectors and earthing switches

GB/T 3804 High-voltage alternating-current load switches for rated voltages 3.6kV to 40.5kV

GB/T 3906 Alternating-current metal-enclosed switchgear and controlgear for rated voltages 3.6kV to 40.5kV

GB/T 11022 Common specifications for high-voltage alternating-current switchgear and controlgear standards

Product Parameters

Parameters

Load switch (C cabinet)

Circuit breaker (V cabinet)

Isolating/earthing switch

Rated voltage (kV)

12

12

12

Rated current (A)

630

630

630

Rated frequency (Hz)

50

50

50

Arc extinguishing mode

Vacuum

Vacuum

/

Power frequency withstand voltage (kV)

Interphase

42

42

42

Relatively

48

48

48

Lightning impulse (kV)

Interphase

75

75

75

Relatively

85

85

85

Rated short-circuit breaking current (kA )/

/

20

/

Breaking times of rated short breaking current/

/

30

/

Rated short-circuit closing current (kA)/peak withstand

50

50

50

Rated short-time withstand current (kA)

20

20

20

Rated short circuit duration (S)

4

4

4

Rated cable charging breaking current (A )/

10

/

/

Arcing time (s)

1

1

1

Partial discharge (Pc)

≤ 5

≤ 5

/

Mechanical life (times)

10,000

10,000

3,000

Applicable environment

Maximum temperature: +60 ℃

Minimum temperature:-40 ℃

Relative humidity: daily average not more than 95%, monthly average not more than 90%

Seismic grade: 8

Altitude: ≤ 1000m