500kW Fixed Fuel Cell Power Station

Negotiable
China
No. 1555 Jingyuan Road, Jiading District, Shanghai City 201800
Online Contact
Favorite
Product Introduction

This series of power stations is entirely designed, developed, and produced by Refire through its proprietary full-process capabilities. With a rated power of 500kW and a peak power of up to 550kW, the power generation efficiency and output voltage platform can be customized according to specific scenarios, supporting combined heat and power generation. The modular architecture allows for the parallel operation of multiple power stations. The skid-mounted structure and containerized layout facilitate rapid deployment and flexible relocation. Equipped with a comprehensive safety system, it supports black start, remote monitoring, and unattended operation. It enables seamless switching between grid-connected and off-grid modes, widely adapting to various energy demands across scenarios such as hydrogen energy storage for peak shaving, industrial energy hubs, data center backup power, commercial complexes, smart communities, and off-grid isolated islands, redefining the application boundaries of distributed energy.

Product Features

  • Ultra-Environmentally Friendly: Zero emissions, low noise

  • High Safety: Comprehensive systematic safety design, including intrinsic safety designs for fire prevention, waterproofing, electric shock protection, electromagnetic compatibility, explosion protection, hydrogen safety, structural safety, functional safety, and full lifecycle safety management regulations

  • High Profitability: Customizable power generation efficiency, capable of combined heat, power, and water supply

  • High Reliability: Three-level verification system, power redundancy design, modular isolation design, uninterruptible power supply

  • Long Lifespan: Self-developed fuel cell system, supports 7*24h operation, lifespan exceeding 40,000 hours

  • Intelligent: Flexible switching between multiple operation modes, automatic warning and protection, remote monitoring and unattended operation

  • High Integration: Skid-mounted design for rapid deployment and flexible relocation

  • High Compatibility: Can operate in parallel with multiple power stations, and can operate in parallel with traditional fuel/gas generator sets or electrochemical energy storage systems

  • Fast Response: Second-level dynamic response, seamless switching between grid-connected and off-grid modes

  • High Adaptability: Lossless rapid start at -30°C low temperature, self-adaptation to high altitudes

Product Parameters

Mechanical Parameters

Integration Form

Integrated: Container A / Container B Integration

(Container A: Power Generation Container, Container B: Electrical Container)

Installation Method

Containerized

Overall Dimensions

≤9000(L)×3000(W)×3000(H) mm

Weight

≤14000 kg

DC Side Parameters

Maximum DC Output Power

660 kW (Standby Version) / 1080 kW (Primary Version)

(Primary Version: Long-duration power generation, Standby Version: Short-duration power generation, Power adjustable)

DC Bus Voltage Range

450~750 VDC

AC Side Parameters

Rated Output Power

500 kW

Maximum Output Power

555 kW

Voltage System

Three-phase three-wire / Three-phase four-wire

Rated Output Voltage

AC 10 kV / 380 V (Customizable)

Power Generation Efficiency at Rated Power Point

13.0~16.0 kWh/kg (Customizable)

Operating Mode

Grid-connected / Off-grid

Cooling Parameters

Cooling Solution

Air-cooled / Water-cooled

Combined Heat and Power (CHP)

Configurable

CHP Hot Water Temperature

≤75℃

Overall CHP Efficiency

≥80%

External Hydrogen Supply Parameters

Hydrogen Supply Pressure Range

≥1.5 Mpag

Hydrogen Supply Quality Requirement

≥99.97%, GB / T 37244

Complete Unit Parameters

Continuous Ramp-up/Ramp-down Rate

(Fuel Cell System Response Only)

60 / 60 kW/s

Instantaneous Ramp-up/Ramp-down Rate

(Supported by Power Battery)

500 / 500 kW/s

Normal Temperature Start-up/Shutdown Time

(Start-up to Rated, Rated to Shutdown, ≥10℃)

≤60 / ≤60 s

Low Temperature Start-up/Shutdown Time

(Start-up to Rated, Rated to Shutdown, ≥-30℃)

≤5 / ≤10 min

Ambient Temperature Range

-30 ~ 45℃

Ambient Altitude Range

≤3000 m

Design Life

≥40000 h

Black Start Capability

Supported

Communication Interface

Ethernet / RS485 / CAN2.0B

Design Standard

GB / T 27748