Generator Breaker Set |
Rated System Source Short-circuit Breaking Current kA |
Rated Generator Source Short-circuit Breaking Current kA |
Low Frequency Breaking Current kA |
Total Breaking Time ms |
Disconnector/Grounding Switch Rated Closing/Opening Time S |
Rated Short-circuit Making Current (Peak) kA |
Rated Short-time Withstand Current / Duration kA/s |
Rated Peak Withstand Current kA |
Rated Current A |
Mechanical Operations Times |
Electrical Life Times |
Remarks |
|
190kA |
195 DC component 85% |
135 DC component 130% |
/ |
≤70 |
≤4 |
535 |
210/3 |
600 |
40000 forced air cooling |
Circuit breaker 6000 disconnector/grounding switch 10000 |
4 |
For nuclear power |
|
170kA |
170 DC component 91% |
135 DC component 130% |
/ |
≤70 |
≤4 |
466 |
210/3 |
600 |
27000 natural cooling 28000 forced air cooling 40000 IPB cooling |
Circuit breaker 6000 disconnector/grounding switch 10000 |
5 |
|
|
160kA |
160 DC component 86% |
130 DC component 130% |
/ |
≤70 |
≤4 |
440 |
Main circuit 160/2 grounding circuit 160/1 |
440 |
25000 natural cooling 27000 forced air cooling |
Circuit breaker 5000 disconnector/grounding switch 10000 |
3 (test report) |
|
|
100kA |
100 DC component 82% |
80 DC component 110% |
/ |
≤60 |
≤4 |
275 |
100/3 |
300 |
15000 natural cooling |
20000 |
8 |
|
|
100kA |
100 DC component 82% |
80 DC component 110% |
55(20~45Hz) |
≤60 |
≤4 |
275 |
100/3 |
300 |
16500 natural cooling |
20000 |
8 |
For pumped storage |
|
Main circuit 100/3 starting/dragging switch circuit 160/3 |
Main circuit 300 starting/dragging switch circuit 480 |
Main circuit 16500 natural cooling starting/dragging switch 4000 |
Circuit breaker/grounding switch 20000 starting/dragging switch 10000 |
|||||||||
|
100kA |
100 DC component 82% |
80 DC component 110% |
/ |
≤60 |
≤4 |
275 |
Main circuit 130/3 starting disconnector 100/3 |
Main circuit 390 starting disconnector 300 |
18000 natural cooling starting disconnector 4000 |
20000 |
8 |
For gas turbine |