Item |
Unit |
Parameter |
|
Rated Voltage |
kV |
±550 |
|
Rated Current |
A |
5000 |
|
Rated Short-time Withstand Current and Duration |
kA,s |
63/2s |
|
Rated Peak Withstand Current (Peak) |
kA |
160 |
|
Rated DC Withstand Voltage to Earth |
kV |
±825 |
|
Rated Lightning Impulse Withstand Voltage |
kV |
1675 |
|
1550±550 |
||
|
Rated Switching Impulse Withstand Voltage |
kV |
1300 |
|
1175±550 |
||
|
SF6 Gas Rated Pressure |
MPa |
0.50 |
|
SF6 Gas Leakage Rate |
%/year |
0.1 |
|
Disconnector, Grounding Switch Mechanical Life |
Times |
5000 |
|
Current Transformer Accuracy Class |
Class |
0.1 |
|
Voltage Transformer Accuracy Class |
Class |
0.1 |