HT33 Series Built-in Isolation Transformer Tower UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Power Range

10~40kVA

Operating Mode

Three-in three-out, double conversion online operation.

Application Fields

Widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Performance Features

Invt tower UPS can be optionally equipped with △/Y isolation transformer at the output end to improve power supply quality, reduce zero-ground voltage, optimize the UPS end power supply network, enhance overload and short circuit protection capability, isolate safe loads, and make the application fields of Invt tower UPS more extensive. Friendly human-machine interface: 3.3-inch LCD non-touch screen, rich in information.

Product Parameters
Model HT33010X-TX HT33020X-TX HT33030X-TX HT33040X-TX
Capacity 10kVA 20kVA 30kVA 40kVA
Main Road Input Input Mode 3P+N+PE
Input Voltage 380/400/415VAC (line voltage)
Power Factor >0.99
Current Distortion Rate THDi<3% (100% linear load)
Voltage Range +25%~-40%
304~485VAC (line voltage) full load, 304~138VAC (line voltage), load linearly derated from 100% to 40%
Frequency Range 40-70Hz
Battery Battery Voltage ±240VDC (30~50 cells)
Charging Power 20% * active power
Bypass Rated Voltage 380/400/415VAC
Voltage Range -20%~+15%
Frequency Range ±5Hz (±1Hz, ±3Hz, ±5Hz)
Rated Output Voltage 380/400/415VAC (line voltage)
Rated Frequency 50/60Hz
Power Factor 0.9
Inverter Overload Capacity 105%, long-term operation; 110%, transfer to bypass after 1 hour; 125%, transfer to bypass after 10 minutes;
150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200ms
System System Efficiency Normal mode ≥92%
Economy mode ≥95%
Battery mode ≥92%
Noise (1 meter) 60dB @100% load, 58dB@45% load
Operating Temperature 0-40℃
Relative Humidity 0-95% (non-condensing)
Altitude <1000m, between 1000~2000 meters, power derated by 1% for every 100 meters increase
Options Dry contact, dust filter, SNMP network communication card, lightning protection module, battery temperature compensator, mobile SMS alarm
Dimensions (W*D*H) mm 350*738*1335 500*840*1400
Weight (kg) 200 220 240 300
Special Note Above 40kVA requires a separate transformer cabinet