Product Introduction

Power range: 1~3kVA

Operating mode: single-in single-out, double conversion online operation.

Application fields: widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Performance features:

High efficiency and energy saving, brand new whole machine design, PF=0.9, whole machine efficiency up to 95.5%, low carbon and energy saving.

Supports lead-acid and lithium batteries, adapting to various application scenarios.

Ultra-compact design, smaller size, more space saving, more flexible installation.

Full digital control charger, charging current can be set 1-12A.

2.7-inch non-touch LCD/LED display, displaying rich machine information.

Black box recording function, recording rectification/inversion abnormal information, can be exported to computer to generate waveform diagrams for easy analysis.

Product Parameters
Model HT1101CL HT1101CS HT1102CL HT1102CS HT1103CL HT1103CS
Capacity 1kVA 1kVA 2kVA 2kVA 3kVA 3kVA
Input Voltage Range 110~300VAC, 50% load @276~300VAC, 100% load @176~276VAC, 100%~50% load linear derating @110~176VAC
Input Power Factor ≥0.99
Frequency Range 50/60±5Hz (default), ±1Hz/±3Hz/±10Hz (settable)
Output Power Factor 0.9
Output Voltage Rated Voltage 220/230/240VAC (PF=0.9)
Voltage Distortion Rate ≤1% THD, linear load, ≤5% THD, non-linear load
Noise (1m in front) <43dB@<60% load, <47dB@>60% load <50dB@<60% load, <55dB@>60% load <50dB@<60% load, <55dB@>60% load
Overload Capacity Main Road Mode 102%~110%: transfer to bypass after 30 minutes; 110%~125%: transfer to bypass after 10 minutes; 125%~150%: transfer to bypass after 30 seconds
Battery Model Depends on external battery 12VDC/9Ah Depends on external battery 12VDC/9Ah Depends on external battery 12VDC/9Ah
Quantity 2 4 6
Maximum Charging Current 1-12A (settable) 1A 1-12A (settable) 1A 1-12A (settable) 1A
DC Voltage 24VDC 48VDC 72VDC
Communication Method RS232, SNMP (optional), USB (optional), RS485 (optional)
Options SNMP card, AS400 dry contact card, emergency shutdown, Type B USB port, RS485 interface, external battery temperature, RJ45 surge protection, lithium battery BMS dry contact
Dimensions W*D*H (mm) 144*350*224 144*410*223 144*410*223 190*405*330
Weight (kg) 4.5 8.5 6 14.1 6 20.5