RM Series 60~600kVA Intelligent Modular UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Power range: 60~600kVA.

Operating mode: three-in three-out, double conversion online operation.

Application fields: widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Performance features include:

·Three-in three-out pure online double conversion product, providing ideal power supply quality and load protection.

·Input power factor up to 0.99, input harmonic current less than 3%, whole machine efficiency greater than 97%, high efficiency and energy saving.
·Adopts DSP full digital control, realizing full digital control of rectification, inversion, charging, and discharging power conversion links.
·With intelligent sleep mode, sleep rotation can be realized by setting rotation time, achieving green energy saving.
·Adopts intelligent multi-stage battery charge and discharge management system.
·Modular design, power modules support hot-swapping, convenient for on-site maintenance.
·Bidirectional DC_DC topology platform, supports charging power up to 30% of useful power.
·Supports simultaneous power supply from battery and grid to load, intelligent peak shifting power supply.
·Intelligent system self-diagnosis solution, rich fault records, large-capacity historical record storage space.
·Standard 10-inch large screen LCD touch screen, rich in information.
·Super strong load adaptability, super strong overload and short circuit capability.
·Battery cell number range 30-48 cells adjustable, supports lithium battery application, flexible configuration and selection.
·Combined inverter power supply design to ensure effective load carrying when mains power drops.
·Digital circulating current control technology, extremely high parallel reliability.
·Panel equipped with EPO emergency shutdown button.
·All circuit boards adopt three-proof technology.
·Super ECO (optional), whole machine efficiency greater than 99%, with reactive power compensation and active power filtering functions, improving input power factor and power supply quality.

Product Parameters

Technical Parameters Table

Model RM600/60D
Capacity 600kVA
Main Road Input Input Mode 3P+N+PE
Input Voltage 380/400/415VAC (line voltage)
Power Factor >0.99
Current Distortion Rate THDi<3% (100% linear load)
Voltage Range 323~478VAC (line voltage), full load, 323~138VAC (line voltage), load linearly derated from 100% to 30%, 323~138VAC (line voltage) + battery combined power supply, load greater than linear derating
Frequency Range 40~70Hz
Battery Battery Voltage ±240VDC (30-48 cells), 30 cells derated to 70%, 32-34 cells derated to 80%, 36-38 cells derated to 90%, 40-48 cells no derating
Charging Power Maximum 15% * active power (100% load rate), maximum 30% * active power (load rate <80%)
Bypass Rated Voltage 380/400/415VAC (line voltage)
Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Output Rated Output Voltage 380/400/415VAC (line voltage)
Rated Frequency 50/60Hz
Output Power Factor 1
Output Total Harmonic Distortion (THDu) <1% (linear load), <5% (non-linear load)
Inverter Overload 110%, transfer to bypass after 1 hour; 125%, transfer to bypass after 10 minutes; 150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200ms
System Main Road Mode Up to 97%
Noise (1 meter) 75dB @ 100% load, 70dB @ 45% load
Operating Temperature 0-40°C
Relative Humidity 0-95% (non-condensing)
Altitude <1000m no derating, between 1000~2000 meters, power derated by 1% for every 100 meters increase
Communication Interface Standard: RS485, USB, CAN, programmable dry contact card, 2 intelligent card slots, one expandable dry contact card slot
Options SNMP card, intelligent AS400 card, parallel components, lightning protection components, main bypass same source components, LBS, RS485 extension card, SMS alarm
Dimensions (W*D*H) mm Host 800*1100*2000
Module 550*750*85 (PM60D)
Weight (kg) Cabinet 443
Module 35.7