RM Series 20~60kVA Integrated Modular UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Operating Mode

Three-in three-out, double conversion online operation.

Application Fields

Widely used in various industry fields such as government, finance, communications, education, transportation, meteorology, radio and television, industry and commerce taxation, medical and health, energy and power, etc.

Performance Features

Supports 20kVA power modules. Optional 3 power modules and 16 pluggable battery pack modules. A single cabinet realizes a modular UPS power supply system integrating high availability, high reliability, flexibility, low cost, and space saving. It can provide about 10 minutes of backup time under full load.

  • The core power devices adopt integrated packaged IGBT modules.
  • The system host is equipped with a 5.7-inch touch LCD display.
  • Hot-swappable static bypass monitoring module.
  • Powerful remote network management solution.
  • Intelligent battery management solution.
  • N+X redundant modular design.
  • Ultra-wide voltage input range.
  • High input power factor.
  • Full digital control.
  • Remote EPO function.
  • Maintenance "zero threshold".
  • Battery cold start function.
  • Maintenance bypass function.

 

Product Parameters
Model RM060/20B
Capacity 20~60kVA
Main Road Input Input Wiring 3-phase + N wire + PE
Input Voltage 380/400/415VAC (line voltage) 220/230/240VAC (phase voltage)
Input Frequency 50/60Hz
Current Distortion Rate THDi < 3% (100% linear load)
Voltage Range 304~485VAC (line voltage) full load, 304~438VAC (line voltage), load linearly derated from 100% to 40%
Frequency Range 40-70Hz
Battery Battery Voltage ±240VDC (30~50 cells)
Charging Power 20% * active power
Bypass Bypass Voltage 380/400/415VAC (line voltage)
Bypass Frequency Range 50/60Hz (rated frequency) ±1Hz, ±3Hz, ±5Hz
Output Rated Output Voltage 380/400/415VAC (line voltage)
Rated Frequency 50/60Hz
Output Power Factor 0.9
Output Total Harmonic Distortion (THDu) <1% (linear load), <5.5% (non-linear load)
Inverter Overload 110%, transfer to bypass after 1 hour; 125%, transfer to bypass after 10 minutes; 150%, transfer to bypass after 1 minute; >150%, transfer to bypass after 200ms
System System Efficiency Normal mode ≥95%, economy mode ≥99%
Communication Interface RS232 RS485 dry contact SNMP card EPO
Operating Temperature 0~40°C
Storage Temperature -25°C~70°C
Relative Humidity 0-95% (non-condensing)
Noise (dB) <55dB
Options SNMP network communication card, lightning protection module, battery temperature compensator, mobile SMS alarm, dust filter, dual input unit, seismic components
Dimensions (W*D*H) mm
Weight
Cabinet (including modules) 600*1020*2000 826kg
PM20 Power Module 440*590*134 (20kVA) Quantity: 3 22kg
Battery Pack Module 120*824*177 Quantity: 16 30kg
PDU Module 440*590*134 Note: When inserting the PDU module, one power module slot is reduced