The FDG-5.3 multi-function fault indicator (LCD version) is widely used in equipment such as ring main units, cable branch boxes, and box-type substations. It detects cable head temperature and short-circuit and grounding faults in real time, transmits data to the host via signal lines, and the OLED screen on the host panel displays the values for easy understanding of line faults and cable head temperature conditions. When short-circuit, grounding faults or temperature overheating occur, and the fault signal or temperature exceeds the threshold, the OLED screen displays the fault status and records it. At the same time, the indicator light gives a fault indication. Fault information can be uploaded via the remote communication interface. Staff can quickly find the faulty line and location based on the fault information, eliminate the fault in time, and restore power supply. With the continuous development and improvement of urban and rural power grid transformation and power supply systems, this product has become an indispensable advanced configuration in urban and rural power grid equipment.
Main Technical Indicators
- 1. Applicable Range: 6-35KV
- 2. Working Power Supply: External DC24-48V universal, built-in rechargeable lithium battery 3.7V 2Ah
- 3. Whole Machine Standby Current: ≤ 5μA
- 4. Temperature Measurement Range: -40℃~200℃ Accuracy: ±2℃
- 5. Overheat Alarm Temperature: 0℃ ~ 150℃ adjustable (factory setting 50℃) Accuracy: ±2℃
- 6. Short-Circuit Fault Current: 1A-1200A adjustable (factory setting 800A) Accuracy: ±20%
- 7. Grounding Fault Current: 1A-200A adjustable (factory setting 10A) Accuracy: ±10%
- 8. Reset Time Range: 1H~99H (factory setting 8h)
- 9. Indicator Protection Level: Host IP40; Sensor IP65
- 10. Working Altitude: ≤3000m
- 11. Ambient Temperature: -40℃ ~ +70℃