The BKM3HU series molded case circuit breaker (hereinafter referred to as the circuit breaker) is a newly launched high-voltage, high-performance thermal-magnetic molded case circuit breaker by our company. The product is suitable for infrequent switching in circuits with AC 50/60Hz, rated operating voltage of AC800V and AC1140V, and rated current up to 630A. This circuit breaker has overload, short-circuit and under-voltage protection functions, which can protect lines and power supply equipment from damage. The product is mainly applied in new energy.
The circuit breaker can be installed vertically (i.e., upright) or horizontally (i.e., sideways).
The circuit breaker has isolation function.
BKM3HU Molded Case Circuit Breaker
Product Introduction
Product Parameters
BKM3HU Main Performance Indicators
|
Model |
BKM 3HU-250 |
BKM 3HU-320 |
BKM 3HU-400 |
BKM 3HU-630 |
|||||
|
Number of Poles |
3 |
||||||||
|
Rated Current In(A) |
63/75/80/100/125/140/160/180/200/225/250 |
125/140/160/180/200/225/250/275/300/315/320 |
225/250/315/350/400 |
400/500/630 |
|||||
|
Rated Insulation Voltage Ui (V) |
1140 |
||||||||
|
Rated Impulse Withstand Voltage Uimp(kV) |
8 |
12 |
|||||||
|
Rated Operating Voltage Ue(V) |
AC800 |
AC1140 |
AC800 |
AC1140 |
AC800 |
AC1140 |
AC800 |
AC1140 |
|
|
Arc Flash Distance (mm) |
⊁100 |
⊁100 |
⊁100 |
⊁100 |
|||||
|
Rated Ultimate Short-circuit Breaking Capacity Icu(kA) |
36.5 |
12 |
50 |
20 |
40 |
15 |
30 |
15 |
|
|
Rated Service Short-circuit Breaking Capacity Ics (kA) |
30 |
12 |
50 |
20 |
36.5 |
15 |
23 |
15 |
|
|
Selectivity Category |
A |
A |
A |
A |
|||||
|
Electrical Life (operations) |
1500 |
1000 |
1500 |
1000 |
1500 |
1000 |
1500 |
1000 |
|
|
Mechanical Life (operations) |
20000 |
20000 |
10000 |
10000 |
|||||
|
Overall Dimensions (mm) |
Width |
113 |
150 |
150 |
182 |
||||
|
Length |
233 |
251 |
329 |
335 |
|||||
|
Height |
114 |
130 |
107 |
110 |
|||||
Note: When applied in photovoltaic grid connection, terminals 1, 3 and 5 of the circuit breaker shall be connected to the transformer side, and terminals 2, 4 and 6 shall be connected to the inverter side.
Other products from this supplier

BKW5 Series Air Circuit Breaker

BKW7 Series Air Circuit Breaker

BKM3 Series Molded Case Circuit Breaker

BKM3L Molded Case Residual Current Circuit Breaker

BKM3Z Intelligent Molded Case Circuit Breaker

BKM5 Series Molded Case Circuit Breaker

BKM5Z Intelligent Molded Case Circuit Breaker

BKB55(L) Miniature (Residual Current) Circuit Breaker

BKB45(L) Miniature (Residual Current) Circuit Breaker

BKB75 Miniature Circuit Breaker

BKC1 Series AC Contactor

BKC1-F AC Contactor
Related Products
ZX1.5-R (27.5 kV) Gas-Insulated Metal-Enclosed Switchgear for Railway Electrification
Advanced Surface Defect Detection System
Automated Chassis
10kV Reactor
YE3 Series Low Voltage High Power Three-Phase Asynchronous Motor
Dry-Type Vacuum On-Load Tap-Changer
550 kV GIS Combined Switchgear
Post-type AC Pollution-resistant Disc Suspension Porcelain Insulator (Triple Umbrella Type)
Electric Energy Metering Box
LEC Series Electrical Control Cabinet
KYN61-40.5 Indoor AC Metal-clad Removable Switchgear