BKM6DC-630V DC Molded Case Circuit Breaker

EXW
$379.59-394.36 /Unit
China
No.266, Chaoyang North Avenue, Xushui District, Baoding City, Hebei Province
0312-5852288
Online Contact
Favorite
Product Introduction

The BKM6DC-630V series DC molded case circuit breaker (hereinafter referred to as the circuit breaker) is suitable for distribution networks with rated insulation voltage of DC2000V, rated operating voltage of DC1500V, and rated current up to 630A. It is used for distributing electrical energy and protecting lines from damage due to overload, short circuit and other faults. The product can be used in DC distribution systems such as new energy, DC energy storage power supplies, power systems, rail transit and electric trams. The circuit breaker can be installed vertically (i.e., upright) or horizontally (i.e., sideways).

The product has the following features:

  • Brand-new modular design significantly increases the capacity of the arc extinguishing system and improves reliability; two-pole structure, non-polar, convenient wiring;
  • High breaking capacity with single-pole full-voltage breaking capability; volume is 50% of traditional 4P products;
  • Power consumption is 60% of traditional 4P products;
  • Low temperature rise, no derating at 55°C;
  • Zero arc flash, high safety.
Product Parameters

Main Performance Indicators

Model

BKM6DC-630V

BKM6DCG-630V

Product Name

Molded Case Circuit Breaker

Isolating Switch

Frame Rating Rated Current Inm(A)

630

630

Rated Current In(A)

200/250/315/350/400/500/630

200/250/315/350/400/500/630

Number of Poles

2

2

Rated Insulation Voltage Ui(V)

DC2000

DC2000

Rated Operating Voltage Ue(V)

DC1500

DC1500

Rated Impulse Withstand Voltage Uimp(kV)

12

12

Arc Flash Distance (mm)

0

0

Rated Ultimate Short-circuit Breaking Capacity Icu(kA)

50

/

Rated Service Short-circuit Breaking Capacity Ics(kA)

20

/

Single-pole Short-circuit Breaking Capacity Iπ(kA)

5

/

Selectivity Category

A

/

Utilization Category

/

DC-23A

Rated Short-circuit Making Current lcm(kA)

/

10

Rated Short-time Withstand Current Icw(kA/1s)

/

10

Electrical Life (operations)

1500

1500

Mechanical Life (operations)

15000

15000

Wiring Method

Front-connected (top or bottom incoming line both acceptable)

Front-connected (top or bottom incoming line both acceptable)

Overall Dimensions
(mm)

Width

98

98

Length (without arc barrier)

256

256

Height

135

135

Note: ① According to GB/T 14048.1, the term "life" indicates the expected number of operating cycles that the apparatus can complete before repair or replacement of parts.