Product Description
FFU is an air circulation purification device that combines a blower and a high-efficiency filter (HEPA/ULPAFite). It is widely used in clean workshop environments to provide clean circulation and temperature control needs of clean workshops.
Applicable Environment
FFU is used in laminar clean rooms, turbulent clean rooms, as well as process equipment and handling equipment. It is suitable for semiconductors, electronic information, optoelectronics, aerospace, pharmaceuticals, etc., and can meet the cleanliness requirements of clean environments CLASS1~10000 in industries that require a clean production environment.

Features

Lightweight modular structure design, suitable for installation of ceiling keels (T-Grid) systems of various manufacturers
High-performance motor, high static pressure, low noise, low energy consumption, can save operating costs.

Special air inlet design, metal air duct structure, smooth surface, low wind resistance, and good sound insulation effect.

Wind guide plate guides 1, wind pressure is evenly diffused, and wind speed on the outlet is stable

With operation/abnormal indicator light and operation/abnormal dry contact for easy monitoring

Single-phase motor can be used for single-speed and three-speed regulation

Various special specifications can be customized
Abnormal indoor fault LED lights can be installed
Pressure differential gauge, wind speed sensor, etc. can be installed

Small remote central monitoring system or large remote central monitoring system can be installed

parameter

Model

CRAFU-T16

CRAFU-T25

CRAFU-T34

Keel size

2 '* 4'

3 '* 4'

4 '* 4'

Box size

(mm)

575*1175*305 W*D*H

875*1175*355 W*D*H

1175*1175*355 W*D*H

Screen size

(mm)

570*1170*50/70 W*D*H

870*1170*50/70 W*D*H

1170*1170*50/70 W*D*H

Air volume

12-16CMM

19-25CMM

21-34CMM

Noise

48-54dB(A)

50-56dB(A)

452-58dB(A)

Fan full pressure

210Pa

220Pa

230Pa

Power consumption

175W

210W

2175w

Weight

35kg

47kg

55kg

Material

Steel plate paint or galvanized sheet or stainless steel

Power

Ac Single Phase Three Phase 220Vor 380V50Hzor60Hz

Speed control function

Three-stage speed regulation or five-stage speed regulation Or variable voltage stepless speed regulation (except three-phase power supply)

filtration efficiency

HEPA9999%@ 0.3um or ULPA999999%@ 0.12um or above

Working status

Power indicating switch operation and fault indicator

Overload protection

Double overload protection for motor and controller

Wiring mode

Terminal block 0r male and female connector or power cord

Monitoring contact