Combined electrical fire monitoring detector
Negotiable
China
No. 6519, Lingang North Road, High-tech Zone, Jinan City, Shandong Province
86 13752227265
Online Contact
Favorite
Product Introduction

SST-DH8000/B combined electrical fire monitoring detector can collect the voltage and current values of the power supply of the monitored fire-fighting equipment, judge and display the working status of the power supply and fault information such as overvoltage, undervoltage, overcurrent, phase loss, and phase error; detect the residual current, temperature and other parameters in the protected line. Once the detector detects that the electrical equipment has leakage or the line temperature is too high, it will issue an audible and visual alarm, effectively ensuring the safety of people's electricity use and preventing the occurrence of electrical fires.

Product Parameters

Name

Parameters

Rated working voltage

AC220V 50Hz

Detection voltage range

AC80~300V

Detection current range

AC0.1A~100A

Detection temperature range

55℃~140℃

Detection residual current range

300mA~999mA

Temperature alarm value

55℃

Residual current alarm value

300mA

Temperature adjustment accuracy

1℃

Residual current adjustment accuracy

1mA

Channel

11 channels (3 channels for voltage, 3 channels for current, 4 channels for temperature, 1 channel for residual current)

Upload method

GPRS/NB-loT/4G-CAT1

Wire system

M-BUS two buses

Overall dimensions

112mm×81mm×66mm

Working temperature

-10℃~55℃

Working humidity

≤93%RH (no condensation)

Implementation standard

GB14287.2—2014、GB14287.3—2014