Model |
INPCS-62.5-MH |
INPCS-75-MH |
INPCS-100-MH |
INPCS-125-MH |
INPCS-200-MH |
|
AC side parameters |
|||||
|
Rated output power (kW) |
62.5 |
75 |
100 |
125 |
200 |
|
Maximum output power (kW) |
75 |
90 |
110 |
150 |
220 |
|
Wiring mode |
3W+N+PE/3W+PE |
||||
|
Output overload capacity (times) |
1.1 @ 45℃ |
||||
|
AC rated current (A) |
90A @ 45℃ |
108A @ 45℃ |
129A @ 45℃ |
180A @ 45℃ |
168A @ 45℃ |
|
AC maximum current (A) |
108A @ 45℃ |
129A @ 45℃ |
163A @ 45℃ |
198A @ 45℃ |
192A @ 45℃ |
|
AC rated voltage (V) |
AC400 |
AC690 |
|||
|
Allowable grid voltage (Vac) |
320~450 |
550~800 |
|||
|
Allowable grid frequency (Hz) |
50/60(-2.5~1.5) |
||||
|
Total current harmonic distortion rate |
≤ 3% (rated power) |
||||
|
Rated power factor |
> 0.99 |
||||
|
Output voltage distortion |
≤ 3% (linear rated power load) |
||||
|
DC side parameters |
|||||
|
Maximum DC power (kW) |
75 |
90 |
110 |
150 |
220 |
|
DC voltage range (Vdc) |
630~950 |
900~1500 |
|||
|
Maximum current (A) |
108A @ 45℃ |
129A @ 45℃ |
163A @ 45℃ |
198A @ 45℃ |
192A @ 45℃ |
|
Withstand short-circuit impulse current |
50kA @ 2ms |
||||
|
Communication Interface |
|||||
|
Communication Interface |
CAN2.0, RS485, Ethernet |
||||
|
Communication Protocol |
ModbusRTU, Modbus-TCP, CAN2.0, TCP/IP |
||||
|
Protection |
|||||
|
AC and DC side lightning protection |
Have |
||||
|
DC side insulation protection |
Have |
||||
|
AC leakage current protection |
Have |
||||
|
AC side protection |
Overcurrent, Overvoltage, Frequency, |
||||
|
DC side protection |
Overcurrent, overvoltage, short circuit, anti-reverse |
||||
|
Over-temperature protection |
Have |
||||
|
AC phase sequence adaptive |
Have |
||||
|
Power module (IGBT) protection |
Have |
||||
|
Communication fault protection |
Have |
||||
|
Cooling system fault protection |
Have |
||||
|
Fault recording |
Not less than 4 cycles, 256 points per week |
||||
|
Active Islanding Detection |
Have |
||||
|
System parameters |
|||||
|
Module main circuit topology |
Three-level interleaved parallel |
||||
|
Operation mode |
Support constant power, constant voltage, constant current control |
||||
|
Number of parallel machines |
8 |
||||
|
Other functions |
PQ, VF, SVG, VSG |
||||
|
Grid-connected and off-grid switching |
Optional |
||||
|
EMI filtering on AC/DC side |
Have |
||||
|
Maximum system efficiency |
≥ 98% |
||||
|
Charge-discharge conversion time (ms) |
≤ 50ms |
||||
|
Noise (dB) |
<75 |
||||
|
Protection level |
IP20/IP65 |
||||
|
Allowable ambient temperature (℃) |
-20 ~ 50 |
||||
|
Cooling mode |
Forced air cooling |
Forced air cooling |
Forced air cooling |
Liquid cooling |
Liquid cooling |
|
Permissible relative humidity |
0 ~ 95% (no condensation) |
||||
|
Allowable Altitude |
No derating below an altitude of 2000m; derating operation between 2000m and 4000m. |
||||
|
Certification Standards |
GBT34120-2017, IEC62477-1 & IEC61000-6-2, -6-4, VDE-AR-N4105 |
||||