VTZ1-40.5(EP) indoor high-voltage AC combined vacuum circuit breaker
Negotiable
China
1688 Danhe East Road, Xiangshan County, Zhejiang Province
+86 0574-59101862
Online Contact
Favorite
Product Introduction

Product features:

① The breaker adopts a wall-passing structure, combined with an isolating switch and a clear break, with a grounding switch installed on the arc-extinguishing chamber side. The grounding switch has short-circuit closing capabilities.

② There is a complete anti-misoperation function between the circuit breaker, isolating switch, and grounding switch, with a cabinet door interlock to achieve the full five-proof function.

③ The vacuum arc-extinguishing chamber can be sealed in the wall-passing pole, with an interrupting capacity of up to 31.5kA.

④ Strong environmental adaptability, with a maximum altitude of up to 4500m and a minimum ambient temperature of -40°C.

⑤ Multiple cables can be connected to the cable outlet.

⑥ Compact switch structure and small size.

Application range:

This product is suitable for the control and protection of the high-voltage side in photovoltaic power generation and wind power dedicated pre-installed substations. It features complete functions and is suitable for operation in high-altitude environments. It can be directly installed in the high-voltage end of pre-installed substations without the need for an additional switchgear cabinet. The interlocking system is reliable, and the performance fully meets the requirements for wind power plants.

The VTZ1-40.5 circuit breaker is also suitable for 40.5kV rated voltage three-phase AC 50Hz indoor switchgear, and is used for protection and control in power distribution systems of wind, solar, energy storage power plants, substations, and industrial and mining enterprises.

Product Parameters

Serial Number

Name

Unit

Parameters

1

Rated voltage

kV

40.5

2

Rated frequency

Hz

50

3

Rated current

A

630, 1250

4

Rated short-time withstand current

kA

20, 25, 31.5

5

Rated short circuit duration

S

4

6

Rated short-circuit breaking current of circuit breaker

kA

31.5

7

Breaker rated short-circuit current breaking times

Times

30

8

1min power frequency withstand voltage: phase-to-ground, phase-to-phase/isolation breaker

kV

95/118

9

Lightning impulse withstand voltage (peak): phase-to-ground, phase-to-phase/isolation breaker

kV

185/215

10

Phase-to-phase center distance

mm

440/470/500

11

Mechanical life: circuit breaker/isolating switch/grounding switch

Times

10000/3000/3000

12

Rated short-circuit closing current of earthing switch

kA

80