Product Advantages

Adopts dry air insulation, vacuum interruption, green and environmentally friendly, zero gauge pressure meets insulation level;

Adopts integrated upper and lower double isolating switches, independent grounding switch, not prone to misoperation.

Visible isolation fracture, improving safety, whole machine partial discharge ≤10pC;

Isolating switches and grounding switches all adopt electric operation, meeting intelligent requirements;

Verified through 5000m high-altitude test;

Meets State Grid 12kV ring main unit (box) standardized design customization scheme.

Suitable occasions and regions

Used in power systems such as miniaturized secondary distribution stations, switching stations, industrial and mining enterprises, urban residential communities, airports, railways, tunnels, high-rise buildings, etc., for receiving and distributing electric energy, greatly improving the reliability and utilization rate of power supply, effectively saving floor space.

Nationwide regions

Product Parameters

Project

Unit

Data

Rated frequency

Hz

50

Rated voltage

kV

12

Short-time (1min) power frequency withstand voltage

To the ground and interphase

kV

45

Interfracture

48

Lightning impulse withstand voltage (peak)

To the ground and interphase

kV

75

Interfracture

85

Partial discharge limit value (test voltage is 1.1Ur)

pC

≤ 10

Rated current

A

630

Rated short-circuit breaking current

kA

20

Number of rated short-circuit breaking current

Times

30

Rated short-time withstand current

kA

20

Rated short circuit duration

S

4

Rated peak withstand current

kA

50

Earthing switch short-circuit closing capacity (double isolation cabinet type)

Times

2

Rated working pressure of dry air (20℃, gauge pressure)

MPa

0.02

Minimum working pressure (20℃, gauge pressure)

MPa

0

Annual leakage rate

%

≤ 0.05

Three-position switch mechanical life

Times

3000

Breaker mechanical life

Times

10000