- Executive Standard: GB/T 9330-2008
- Applications: Suitable for control and monitoring circuits, protection lines, and other occasions with AC rated voltage 450/750V and below.
- Operating Conditions:
- The long-term allowable operating temperature of the cable conductor is 70°C.
- The cable laying ambient temperature shall not be lower than 0°C.
- Allowable bending radius of the cable:
For non-armored cables, not less than 6 times the cable outer diameter.
For armored or copper tape shielded cables, not less than 12 times the cable outer diameter.
For flexible cables with shielding structure, not less than 6 times the cable outer diameter.