MISELA/NISELA 12kV-72.5kV Gas-insulated Switchgear
Negotiable
China
National (Xuchang) Power Electronics System Industrial Park, Yangguang Avenue, Weidu District, Xuchang City, Henan Province
0374-3216642
Online Contact
Favorite
Product Introduction

The MISELA/NISELA series gas-insulated switchgear (C-GIS) is the latest generation product based on internationally advanced solid insulation technology, gas insulation technology, vacuum interruption technology, modular plug-in technology, integrated voltage equalization-cooling technology, phase-change heat dissipation technology, combined with automated welding technology and helium leak detection process.

Performance Features

◆ Complies with relevant Chinese standards: GB3906, GB/T11022, DL/T593, DL/T404, etc., and international standards IEC62271-200 and IEC62271-100, etc.;

◆ Compact 12kV switchgear typical cabinet width minimum not exceeding 500mm; 24kV, 40.5kV switchgear typical cabinet width not exceeding 600mm, small cabinet size, small footprint;

◆ High-voltage components enclosed inside a sealed gas chamber, waterproof, dustproof, unaffected by environment, unaffected by altitude, completely maintenance-free; circuit breaker adopts spring operating mechanism; solid-sealed pole vacuum arc-extinguishing chamber, greatly reduced number of parts;

◆ Three-position switch has manual and electric operation functions, with mechanical and electrical interlocking with the circuit breaker;

◆ Adopts intelligent control and protection unit with control, protection, measurement, and communication functions, fully realizing distribution network automation requirements; has reliable mechanical and electrical interlocking design scheme, effectively preventing misoperation;

◆ Switchgear intervals adopt top rigid busbar expansion, convenient installation, flexible expansion, and no need to handle the gas system;

◆ World-class manufacturing technology, laser cutting, automated welding, helium leak detection; processing equipment imported from Germany, German acceptance, strictly implementing production processes from Germany, ensuring fault-free operation of the switchgear.

Product Parameters

12kV -40.5kV gas insulated switchgear

Indicator Item

Unit

Parameters

Rated voltage

kV

12

24

27.5

40.5

Rated current

A

1250

2500

3150

4000

1250

2500

1250

2500

1250

2500

3150

4000

Rated frequency

Hz

50/60

50/60

50/60

50/60

Rated short-time power frequency withstand voltage (phase-to-phase, to ground/fracture)

kV

42/42/48

65/65/79

95/140/118

95/95/118

Rated lightning impulse withstand voltage (phase-to-phase, to ground/fracture)

kV

75/75/85

125/125/145

200/325/220

185/185/215

Rated short-time withstand current and time

kA/s

25/4, 31.5/4

Apr-40

25/4, 31.5/4

31.5/4

25/4, 31.5/4

31.5/4, 40/4

Rated peak withstand current

kA

63, 80

100

63, 80

80

63, 80

80, 100

Insulating gas

-

SF6, dry air

SF6, dry air

SF6, dry air

SF6, dry air

SF6

Rated inflation pressure (relative pressure at 20℃)

MPa

0.02

0.02

0.03

0.03

Minimum working pressure (relative pressure at 20℃)

MPa

0

0

0

0

Rated operating sequence

1

O-0.3s-CO-180s-CO

O-0.3s-CO-180s-CO

O-0.3s-CO-180s-CO

O-0.3s-CO-180s-CO

Protection level

Gas box

-

IP67

IP67

IP67

IP67

 

Cabinet

-

IP4X

IP4X

P4X

P4X

Breaker mechanical life

Times

10000/20000/300000

10000/200003000

20000

10000/20000/300000

Rated voltage of auxiliary circuit

V

DC48/110/220 AC110/220

DC48/110/220 AC110/220

DC48/110/220/AC110/220

DC48/110/220/AC110/220

Overall dimension (W×D×H)

mm

1250A:500/600 × 1300 × 2400

2500A:800 × 1700 × 2400

3150A:800 × 1700 × 2400

4000A:900 × 1800 × 2400

1250A:600 × 1300 × 24002500A:800 × 1700 × 2400

1250A:600 × 1700 × 24002500A:800 × 1700 × 2400

1250A:600 × 1700 × 2400 2500A:800 × 1700 × 24003150A:800 × 1700 × 2400 4000A:900 × 1800 × 2400

72.5kV gas insulated switchgear

Indicator Item

Unit

Parameters

Rated voltage

kV

72.5

Rated current

A

1250

Rated frequency

Hz

50/60

Rated short-time power frequency withstand voltage (phase-to-phase, to ground/fracture)

kV

160/160/202

Rated lightning impulse withstand voltage (phase-to-phase, to ground/fracture)

kV

380/380/439

Rated short-time withstand current and time

kA/s

31.5/431.5/4, 40/4

 

 

 

Rated peak withstand current

kA

8080, 100

Insulating gas

-

SF6

Rated inflation pressure (relative pressure at 20 ℃)

MPa

0.04

Minimum working pressure (relative pressure at 20 ℃)

MPa

0.02

Rated short-circuit closing current

kA

80, 80, 100

Rated operating sequence

-

O-0.3s-CO-180s-CO

Protection level

Gas box

-

IP67

 

Cabinet

-

IP4X

Breaker mechanical life

Times

10000

Rated voltage of auxiliary circuit

V

DC48/110/220/AC110/220

Overall dimension (W×D×H)

mm

1000*2000*2450