LDBM-12kV Armored Removable AC Metal-enclosed Switchgear

Negotiable
China
National (Xuchang) Power Electronics System Industrial Park, Yangguang Avenue, Weidu District, Xuchang City, Henan Province
0374-3216642
Online Contact
Favorite
Product Introduction

Product Advantages:

Complete Product Series

  • LDBM-12 switchgear provides a complete product series with rated current from 630A to 5000A and short-circuit breaking current from 20kA to 50kA.
  • Flexible solutions: Comprehensive primary schemes to meet various user needs.
  • Excellent compatibility: Compatible with multiple specifications of vacuum or gas circuit breakers, contactors, and other functional handcars from domestic and international sources, with 100% interchangeability for handcars of the same specification.

Rigorous Quality Control System

  • Committed to customer-oriented total quality management philosophy, strictly implementing the comprehensive quality management system (TQMS) of ISO 9001-2000, ISO 14001-1996, and OHSAS 18001-1999; every switchgear completes factory testing in accordance with standards such as GB 3906 and GB 1984;
  • The full series of products has not only passed internal tests but also undergone arc, pollution, condensation, EMC, and vibration tests at authoritative third-party testing institutions;
  • The full series of products has passed complete type tests at authoritative third-party testing institutions, meeting air clearance greater than 125mm and the 18 anti-misoperation measures of the State Grid.

Extremely High Safety

  • Fully enclosed cabinet structure with complete isolation of functional units, thorough separation of high and low-voltage areas, and handcar and grounding switch operations possible only when all cabinet doors are closed, effectively ensuring operator safety;
  • Provides complete mechanical interlocking functions with a simple and reliable bidirectional five-prevention interlocking device, reliably preventing misoperation to ensure personnel and equipment safety;
  • IAC-level cabinet design: Cabinet structure meets 31.5kA/1s and 40kA/1s arc requirements, with independent upward pressure relief channels and three-layer filtered pressure relief devices in each compartment; the pressure relief device reliably opens during internal arc faults, effectively preventing internal arcs from escaping from the front and sides of the cabinet to harm nearby personnel.

Extremely High Reliability

  • Insulation performance: Equipment adopts air insulation or composite insulation measures, meeting standard requirements for power frequency withstand voltage, lightning impulse, and partial discharge;
  • Partial discharge level: Whole cabinet partial discharge value ≤50pC at 1.1Ur;
  • Temperature rise control: Adopts heat-dissipating contact box and integrated static contact technology, achieving natural cooling for 3150A specifications and requiring only one fan with power less than 200W for 4000A specifications.

Excellent Convenience

  • Ample cable compartment space with installation height up to 700mm or more, allowing connection of multiple cables;
  • Circuit breaker handcar and grounding switch can be electrically operated, reducing operation and maintenance costs;
  • Instrument compartment component mounting plate and terminal mounting plate adopt rotary structure, facilitating maintenance and installation of secondary components.
Product Parameters

No.

Project

Unit

Numerical

1

Rated voltage

kV

12

2

Rated Insulation Level

Short-time power frequency interphase, relative ground

Withstand voltage vacuum fracture and isolation fracture

Lightning impulse resistance phase, relative to the ground

Voltage (peak) vacuum fracture and isolation fracture

42

48

75

85

Auxiliary and control loop short-time power frequency withstand voltage

2

3

Rated frequency

Hz

50

4

Rated current of main bus

A

630~5000

5

Rated current of branch bus

630~5000

6

Rated short-circuit breaking current

kA

20 to 50

7

Rated short-circuit closing current (peak)

50 to 125

8

Rated short-time withstand current

20 to 50

9

Rated peak withstand current

50 to 125

10

Rated short circuit duration

S

4

11

Breaker mechanical life

Times

30000

12

Mechanical life of earthing switch

Times

3000

13

Electrical life of earthing switch

Times

2

14

Degree of protection (external/inter-compartment)

 

IP4X/IP2X

15

Internal Arc Test Features

Internal arc rating

 

IAC

Types of accessibility

 

BFLR

Current for arc test

kA

25

31.5

40

Duration of arc test current

S

1

1

1

 

Rated current Ie

Width (W)

High (H)

Deep (D)

Ie <2000A

800

2300

1500 (cable)

1700 (overhead)

2000A≤Ie ≤5000A

1000

2300

1500 (cable)

1800 (cable/overhead)