High-voltage Switchgear

Negotiable
China
Room 908, 9th Floor, Building 1, Yard 2, Jinze West Road, Fengtai District, Beijing, 100073, P.R. China
15210760531
+86 18910035135
Online Contact
Favorite
Product Introduction

KYN28A-12 Metal-clad Removable AC High-voltage Switchgear is a complete distribution device for 3–12kV, three-phase AC 50Hz single-busbar and single-busbar sectionalized systems. It is used in power plants, small- and medium-sized generator transmission, industrial/mining/enterprise power distribution, secondary substation power receiving and distribution in power systems, and large high-voltage motor starting, etc., to achieve control, protection, and monitoring functions. The switchgear can be equipped with ABB's VD4 vacuum circuit breaker or domestic VS1 vacuum circuit breaker, making it a high-performance distribution device.

Key Features

Cabinet structure made of aluminum-zinc coated steel sheet processed by CNC machine tools using multiple bending technology and then bolted together

All operations performed with cabinet doors closed

High protection level effectively prevents ingress of debris and pests

Simple and effective "five-prevention" interlocks to prevent misoperation

Compatible with VS1 and VD4 vacuum circuit breakers

Simple circuit breaker replacement with excellent handcart interchangeability

Reliable wall-mounted installation and front-maintenance design, reducing floor space

Ample cable compartment space allowing connection of multiple cables

Optional heaters in breaker compartment and cable compartment to prevent condensation and corrosion

Applicable Standards

GB/T 3906; IEC 298

Product Parameters

Technical parameters

Technical parameters of switch cabinet

Project

Parameters

Rated voltage (kV)

3,6,10

Power frequency withstand voltage (kV)

42

Lightning impulse (kV)

75

Rated frequency (Hz)

50

Rated current of main bus (A)

630,1250,1600,2000,2500,3150,4000

4 seconds thermal stability current (effective value) kA

16,20,25,31.5,40,50

Rated dynamic stability current (peak) * kA

40,50,63,80,100,125

Protection level

Enclosure Shell IP4X, IP2X when compartment, breaker room door is open

Main technical parameters of vacuum circuit breaker

Rated voltage (kV)

10

Rated frequency (Hz)

50

Rated current (kA)

630-4000

Power frequency withstand voltage (kV)

42

Lightning impulse (kV)

75

Mechanical life (times)

3000

Applicable environment

Maximum temperature: +60 ℃

Minimum temperature:-40 ℃

The relative humidity shall not exceed 95% per day and 90% per month.

Seismic grade: 8

Altitude: ≤ 1000 m