Product Overview
The PCS-901 series is a digital ultra (extra) high-voltage transmission line complete rapid protection device. It is equipped with pilot protection based on power-frequency variation directional and zero-sequence directional elements, unique power-frequency variation distance protection, and a full set of backup protection consisting of three-stage phase-to-phase and ground distance protection plus multi-stage zero-sequence directional overcurrent protection. It also includes automatic reclosing functionality and can serve as primary and backup protection for 220kV and above transmission lines. The device fully supports digital substation functions, IEC 61850-9-2 sampling value transmission protocol, IEC 61850 communication protocol, and real-time GOOSE functionality.
Product Functions
Protection Functions
Pilot power-frequency variation directional protection
Pilot zero-sequence directional protection
Power-frequency variation distance protection
Three-stage phase-to-phase distance protection
Three-stage ground distance protection
Two-stage zero-sequence directional overcurrent protection
Phase overcurrent protection upon PT disconnection
Zero-sequence overcurrent protection upon PT disconnection
Inconsistency protection
Distance and zero-sequence acceleration protection
Oscillation blocking
Automatic reclosing
Supports multiple pilot communication modes including power-line carrier, optical fiber, etc.
Auxiliary Functions
Online hardware and loop detection
Fault location
Minute pulse, second pulse, and IRIG-B time synchronization
256 event reports, 64 fault recording reports
Diverse communication solutions supporting power industry standards IEC 60870-5-103 and IEC 61850
User-friendly HMI with convenient supporting debugging software and powerful waveform analysis tools