(Copper / Aluminum Alloy Core) Extruded Insulated Power Cable
Negotiable
China
Building 2, No.1148 Waiqingsong Highway, Anting Town, Jiading District, Shanghai
18116493402
18621662486
Online Contact
Favorite
Product Introduction

This product is suitable for fixed installation on AC 50 Hz transmission and distribution lines with rated voltage of 1.8/3kV or 0.6/1kV and below.

The power cable products produced by our company comply with the national standard GB/T 12706.1-2020 (equivalent to the international standard IEC 60502-1:2004) and GB/T 31840.1-2015; for overseas users, they can be produced according to British standards (BS), German standards (DN) and other national standards. In addition, power cable products with special properties can also be designed and manufactured according to user requirements.

Product Parameters

Main performance of cable

1. DC resistance of conductor (Ω/km)

Nominal section (mm²)

Maximum DC resistance of conductor at 20℃

Nominal section

(mm²)

Maximum DC resistance of conductor at 20 ℃

Nominal section (mm²)

Maximum DC resistance of conductor at 20℃

Cu

AI

Cu

AI

Cu

AI

1.5

12.1

...

35

0.524

0.868

240

0.0754

0.125

2.5

7.41

...

50

0.387

0.641

300

0.0601

0.100

4

4.61

...

70

0.268

0.443

400

0.0470

0.0778

6

3.08

...

95

0.193

0.320

500

0.0366

0.0605

10

1.83

3.08

120

0.153

0.253

630

0.0283

0.0469

16

1.15

1.91

150

0.124

0.206

800

0.0221

0.0367

25

0.727

1.20

185

0.0991

0.164

1000

0.0176

0.0291

2.AC voltage test

0.6/1kV power cables shall be subjected to 3.5kV power frequency test voltage for 5min without breakdown; 1.8/3kV power cables shall be subjected to 6.5kV power frequency test voltage for 5min without breakdown.