HTC11-W Series Industrial Dedicated 1-3kVA Online UPS

Negotiable
China
INVT Guangming Technology Building, Songbai Road, Matian Street, Guangming District, Shenzhen City, Guangdong Province
13532199679
13532199679
Online Contact
Favorite
Product Introduction

Power range: 1~3kVA

Operating mode: single-in single-out, double conversion online operation.

Application fields: used in IT computer rooms, railway transportation, precision instruments, wind power energy storage and other fields.

Performance features:

High efficiency and energy saving: output PF=0.9, whole machine efficiency up to 95.5%, low carbon and energy saving.

Wide temperature backup battery: adapts to various high and low temperature application scenarios, high power, long life.

High-level electromagnetic protection: surge meets ±4kV/2kV, high lightning protection.

Full digital control charger: charging current supports manual adjustment, current range 1-12A.

Strong load adaptability: supports inductive and capacitive loads, flexible application.

Wide temperature LCD/LED display: can work normally in low temperature conditions, displaying rich machine information and operating status.

Black box recording function: records rectification/inversion abnormal information, can be exported to computer to generate waveform diagrams for easy analysis.

High protection level: enhanced three-proof coating, improving the corrosion resistance of the power board.

Product Parameters
Model HT1101CS-W HT1101CL-W HT1102CS-W HT1102CL-W HT1103CS-W HT1103CL-W
Capacity 1000VA/900W 1000VA/900W 2000VA/1800W 2000VA/1800W 3000VA/2700W 3000VA/2700W
Cold Start Function Have, output defaults to 50Hz
Input Voltage Range 110~300VAC, 50% load @276~300VAC, 100% load @176~276VAC, 100%~50% load linear derating @110~176VAC
Input Power Factor ≥0.99
Frequency Range 50/60±5Hz (default), ±1Hz/±3Hz/±10Hz (settable)
Output Voltage Power Factor 0.9
Output Frequency Output frequency adaptive (settable)
Rated Voltage 220/230/240VAC
Dynamic Response ≤5% (0% - 100% - 0%)
Dynamic Recovery ≤40ms (0% - 100% - 0%)
Voltage Distortion Rate ≤1% THDu, linear load, ≤5% THDu, non-linear load
Transfer Time Main road to battery 0
Inverter to bypass 2ms
Crest Factor 3:01
Whole Machine Efficiency 94.5%@100% load 95%@100% load 95.5%@100% load
Noise (1m in front) <43dB@<60% load, <47dB@>60% load <50dB@<60% load, <55dB@>60% load <50dB@<60% load, <55dB@>60% load
Overload Capacity Main Road Mode 102%~110%: transfer to bypass after 30 minutes; 110%~125%: transfer to bypass after 10 minutes; 125%~150%: transfer to bypass after 30 seconds
Battery Mode 89.5%@100% load 91.5%@100% load 91.5%@100% load
Battery Model 12VDC/9Ah Depends on external battery 12VDC/9Ah Depends on external battery 12VDC/9Ah Depends on external battery
Quantity 3 6 8
Maximum Charging Current 1A 1-12A (settable) 1A 1-12A (settable) 1A 1-12A (settable)
DC Voltage 36VDC   72VDC   96VDC  
Communication Method RS232, SNMP (optional), USB (optional), RS485 (optional)
Options SNMP card, AS400 dry contact card, USB, RS485, EPO, external battery temperature, RJ45 surge protection, BMS, remote shutdown
Dimensions W*D*H (mm) 144*350*224 190*405*330 144*410*223 190*405*330 144*410*223
Weight (kg) 12.6 4.5 24.7 6 30.6 6
Ambient Temperature -30~60°C. When the UPS operating ambient temperature exceeds 40°C, the load is derated by 2% for every 1°C increase.
Altitude No derating within 1000m, derated by 1% for every 100m increase between 1000~3000m.