DN15 Gas Emergency Shut-off Valve

Negotiable
China
Technology Accelerator Building A-5, No.222 Weiwu Road, Yueqing Economic Development Zone, Yueqing City, Wenzhou City, Zhejiang Province, China
13616877222
Online Contact
Favorite
Product Introduction

Product Model: DN15 Gas Emergency Shut-off Valve
Product Type: Gas Solenoid Shut-off Valve / Gas Safety Emergency Shut-off Device
Manufacturer: Zhejiang WEAJA Electronic Technology Co., Ltd.
Applicable Gases: Natural Gas, Liquefied Petroleum Gas (LPG)
Application Fields: Gas Engineering, Urban Gas, Industrial Gas, Boiler Rooms, Catering Gas, Commercial Gas Safety Systems
I. Product Overview

DN15 Gas Emergency Shut-off Valve is an automatic shut-off device for gas pipeline safety control developed and manufactured by Zhejiang WEAJA Electronic Technology Co., Ltd. It is mainly used to quickly and urgently shut off the gas pipeline in emergency situations such as gas leakage, over-limit alarm, or system abnormality to prevent the expansion of gas accidents and ensure the safety of the gas environment.

The product can be used in conjunction with gas alarms, gas detectors, and gas safety control systems. When gas leakage is detected or the set alarm threshold is reached, the shut-off valve can automatically close the gas source within 1 second. It also supports manual closing and manual reset opening. The structure is reliable and suitable for various gas engineering projects such as residential gas, commercial kitchens, industrial gas equipment, etc.

II. Product Core Advantages

Suitable for common gas media such as natural gas and liquefied petroleum gas

DC pulse drive, no power consumption when power is off, safe and reliable

Valve closing time < 1 second, quickly cuts off the gas source

Supports linkage with gas alarms and gas detectors

Supports manual valve closing + manual reset opening for convenient emergency handling

Aluminum alloy valve body, lightweight structure and corrosion resistant

Explosion-proof certification Ex mb IIC T4 Gb, suitable for explosion-proof places

Complies with national explosion-proof implementation standard GB3836.9-2014
III. Typical Application Scenarios

Emergency Shut-off at the Household End of Urban Gas Pipeline Networks

Commercial Kitchens and Catering Gas Safety Systems

Supporting Industrial Boiler Rooms and Gas Heating Equipment

Gas Pipeline Safety Control in Chemical Plants and Gas Stations

Forms a gas safety system in conjunction with gas alarms and gas detectors

IV. System Linkage Instructions

The DN15 Gas Emergency Shut-off Valve can be used with combustible gas detectors and gas alarm controllers. When gas leakage exceeds the limit, the control system outputs a pulse signal to drive the shut-off valve to quickly close the gas channel, realizing the linkage closed-loop control of "detection—alarm—shut-off" and improving the overall safety level of the gas system.

V. Installation and Usage Points

Before installation, please confirm that the pipe diameter specification matches the threaded connection method

The shut-off valve should be installed before the gas meter or at key positions of the main gas pipeline

After closing, manual reset is required to reopen the gas supply

It is recommended to use in conjunction with a gas detection and alarm system to form a complete safety protection system

Product Parameters

Technical Parameters

Item Parameter Description
Nominal Diameter DN15
Applicable Gas Natural Gas, Liquefied Petroleum Gas (LPG)
Working Pressure 0~100 kPa
Valve Body Material Aluminum
Connection Method G1/2, G3/4, G1 Pipe Thread
Valve Closing Method DC Pulse Drive / Manual Valve Closing
Valve Opening Method Manual Reset
Valve Closing Time < 1 second
Drive Voltage DC 9V~12V (pulse)
Drive Current ≤ 1.5A (pulse)
Outlet Length ≥ 0.4 m
Explosion-proof Mark Ex mb IIC T4 Gb
Implementation Standard GB 3836.9-2014