GT-SST610LED-E Point-Type Combustible Gas Detector

EXW
$100.00-101.00 /pcs
China
No. 169, Helin Street, Gaoxin District, Jinan of China
86 13752227265
Online Contact
Favorite
Product Introduction

Product Description:

The GT-SST610LED-E gas detector adopts a two-wire non-polar power supply and signal transmission mode, featuring easy installation and convenient wiring. It continuously monitors methane gas within the lower explosive limit (LEL) range in industrial and commercial environments. Meanwhile, it converts gas concentration and system information into digital signals, which are then transmitted to the gas alarm controller system for identification, display, and processing.

 

Product Features:

※ The detector adopts high-quality gas-sensing elements, featuring stable performance, high sensitivity, strong anti-interference capability and good anti-toxicity resistance.

※ It is equipped with an LCD for on-site concentration display and LEDs for on-site status indication: the green LED is on for "Normal", the yellow LED is on for "Fault", and the red LED is on for "Alarm".

※ It can be zero-calibrated and calibrated through the matched controller.

※ The detector has a built-in infrared receiving module, and on-site settings such as zero calibration and calibration can be performed via an infrared remote control.

※ The sensor module adopts a hot-swappable design, which facilitates installation and maintenance. After replacing the module, it can be used directly without re-calibration.

 

Application Scenarios:

Widely applied in large shopping malls, large restaurants, food processing factories, pharmaceutical factories, automobile manufacturing plants, small industrial and commercial users (small venues such as snack bars, hairdressing and beauty salons, hotels, public bathhouses and Internet cafes), farmers' markets and other industrial and commercial premises where gas leakage may occur.

技术参数
Rated Voltage DC 24V
Detected Gas Methane
Detection Principle Catalytic Combustion, Infrared
Response Time T90 ≤ 30s
Error ±3% LEL
Communication Method M-BUS Two-Wire Bus
Display Type None
Resolution 1%LEL
Power Consumption ≤ 1W
Measuring Range 3% LEL~100% LEL
Alarm Method Indicator Light (Explosion-Proof Audible and Visual Alarm Light Optional)
Operating Temperature -40°C~70°C
Operating Humidity ≤ 96% RH (No Condensation)
Pressure Range 86kPa~106kPa
Installation Method Fixed Bracket Type, Pipe-Mounted Type, Wall-Mounted Type
Installation Thread G3/4" Internal Thread
Dimensions 155mm×150mm×80mm
Explosion-Proof Mark Ex db II C T6 Gb; Ex tb III C T80°C Db
IP Rating IP66
Executive Standard GB 15322.1-2019