Product Introduction

The XY900_DR explosion-proof human machine interface is equipped with a 32-bit 800MHz RISC CPU and a Linux kernel. It supports most PLCs in industrial control systems. Its outstanding processing speed and rich software features meet user requirements, making it widely used in petroleum, chemical, pharmaceutical, and other hazardous environment industries.

Advantages:

  • All-metal explosion-proof enclosure, fully certified as a complete unit
  • Explosion-proof designed touchscreen with electrostatic discharge protection, operable directly in hazardous areas, corrosion-resistant touch panel, meeting harsh environment requirements
  • No electrical exposure in internal wiring
  • Can be equipped with an external explosion-proof USB sleeve, supporting external USB data access
  • Explosion-proof light, explosion-proof power switch, reset button, emergency stop button, USB interface
  • Industrial-grade design standards, high reliability and stability.
  • Operating ambient temperature: -40°C~+60°C
  • Explosion-proof design, suitable for explosive gas atmospheres Zones 1 and 2, and explosive dust atmospheres Zones 21 and 22
  • Suitable for hydrogen environments

Product Parameters

Model XY900_12DR
Type Human Machine Interface (HMI)
Screen Type TFT_LCD/LED backlight
Screen Size 12 inches
Resolution 800*600
Screen Colors 16.77M colors
Brightness 450 nits
Backlight 50000 hours
Operation Mode Touchscreen
Central Processing Unit (CPU) ARM RISC 32-bit 800MHz
Memory 128M NAND flash, 128M DDR3 DRAM
Expansion Storage 1 USB host (≤16G)
Communication Interface 1 10M/100M Ethernet RJ45 port
2 RS232/RS485/RS422
USB 3 USB hosts: upload/download programs and store data
1 USB slave: upload/download programs and configure HMI system parameters
Configuration Software XYFD2000
Program Download Supports local download via USB drive/USB port/network port
Operating Temperature Normal: 0-50℃/Low: -20~60℃/Wide: -40~55℃
Storage Temperature -10~60℃/-40~70℃
Ambient Humidity 10~90% relative humidity (non-condensing)
Voltage Rating 24V DC, operating range 21~28V DC
Rated Power 10W, max 12W
Electrical Interface 4 M20 explosion-proof sealed cable glands
Protection Rating IP66
Explosion-Proof Marking XY900: Ex ib nR IIC T6 Gc; Ex ib tb IIIC T80°C Db