Grade 1E category K3 /K1, low-smoke , halogen-free and flame-retardant insulated wire for Nuclear Power Plant Cable
Negotiable
China
No. 18, Science and Technology Avenue, Electronic Technology Industrial Park, Changzhou High-tech Zone, Jiangsu
+86 519 85480080
Online Contact
Favorite
Product Introduction

Properties

1  Rated voltage:0.6/1kV

2  The permitted long-term working temperature of conductor: 90℃.

3 The permitted bending radius of cable is no less than 6 times of the overall diameter of the cable .

4  The Min. environmental temperature:-35℃. (Ambient temperature can be due to customer demand)

5 Min. laying temperature of the cable is 0℃. The cable should be pre-heated if it is below the Min. laying temperature

6  Normally service life: at least 40 years or 60 years.

7  Combustibility

7.1 The insulated core can pass the test according to GB/T 18380.12(IEC60332-1): Test method on electric wires or cables under fire conditions.

8  The cable can comply with he test according to GB/T 17651(IEC 61034):Test method on electric wires or cables under fire conditions.

9  Insulation material and sheath material of the cable should be tested as per GB/T 17650(IEC 60754-2), which pH is no less than 4.3, and conductivity should be less than 10s/mm.

10  Electrical properties:

10.1   It can withstand AC 3500V/5min.

10.2 DC resistance of conductor at 20℃and insulation resistance at 20℃and 90℃