Overview:

The ZW8-12 series vacuum circuit breaker is a high-voltage outdoor switchgear designed for a rated voltage of 12kV and three-phase AC systems with a frequency of 50Hz. It is primarily used for breaking and closing load currents, overload currents, and short-circuit currents in rural power grids, urban power grids, and small power systems.

The product features a three-phase common box structure, with the three-phase vacuum interrupter housed within a metal box. SMC insulation materials are used for phase-to-phase insulation and grounding insulation, ensuring reliable performance and high insulation strength.

 
 
Technical Specifications

 

Item Unit 6.3kA 12.5kA 20kA
Rated Voltage kV 12 12 12
Rated Current A 630 630 630
Rated Short-Circuit Breaking Current kA 6.3 12.5 20
Rated Short-Circuit Closing Current (Peak) kA 16 31.5 50
Rated Peak Withstand Current kA 16 31.5 50
Rated Short-Time Withstand Current kA 6.3 12.5 20
Rated Insulation Level        
Lightning Impulse Withstand Voltage (Peak) kV 75 75 75
1-Minute Power Frequency Withstand Voltage kV 42 42 42
Rated Operating Sequence   Open-0.3s-Close Open-180s-Close Open    
Mechanical Lifespan Times 10,000 10,000 10,000
Rated Short-Circuit Breaking Current Breaking Times Times 30 30 30
Operating Mechanism Rated Closing Voltage V 110/220 110/220 110/220
Operating Mechanism Rated Opening Voltage V 110/220 110/220 110/220
Contact Opening Distance mm 11 ± 1 11 ± 1 11 ± 1
Overtravel (Contact Spring Compression Length) mm 3 ± 0.3 3 ± 0.3 3 ± 0.3
Three-Phase Closing Non-Simultaneity ms ≤2 ≤2 ≤2
Contact Closing Bounce Time ms ≤2 ≤2 ≤2
Average Opening Speed m/s 1.0 ± 0.2 1.0 ± 0.2 1.0 ± 0.2
Average Closing Speed m/s 0.7 ± 0.15 0.7 ± 0.15 0.7 ± 0.15
Opening Time at Maximum Operating Voltage ms 15-50 15-50 15-50
Opening Time at Minimum Operating Voltage ms 30-60 30-60 30-60
Closing Time ms 25-50 25-50 25-50
Resistance of Each Phase Main Circuit μΩ ≤120 (with G ≤200) ≤120 (with G ≤200) ≤120 (with G ≤200)
Allowable Cumulative Wear Thickness of Moving and Static Contacts mm 3 3 3
Weight kg 152 (with G 180) 152 (with G 180) 152 (with G 180)