Overview:

The ZW32-40.5F(M) outdoor high-voltage intelligent (permanent magnet) vacuum circuit breaker primarily consists of integrated solid-sealed poles, current transformers, an operating mechanism, and a steel enclosure. An isolation switch can be added if needed. This circuit breaker is designed with compactness in mind, using a high-quality steel box for its casing. The current transformer can be selected based on user requirements.

This device is mainly used in medium-voltage overhead line networks for breaking and closing load currents, overload currents, and short-circuit currents.

Operating Conditions:

  • Ambient air temperature: -30°C to +60°C;
  • Altitude: not exceeding 3000 meters;
  • Wind speed: not exceeding 34 m/s;
  • External vibrations or ground movements affecting the switchgear and control equipment are negligible;
  • Pollution level: Grade IV;
  • Storage temperature: -40°C to +85°C.
Technical Specifications

 

Item Unit Parameter
Rated Voltage kV 40.5
Rated Current A 1250 / 1600
Rated Frequency Hz 50 or 60
Power Frequency Withstand Voltage (1 min)    
Wet (Phase-to-Phase, to Ground/Across Open Contacts) kV 80
Dry (Phase-to-Phase, to Ground/Across Open Contacts) kV 95
Lightning Impulse Withstand Voltage (Peak) (Phase-to-Phase, to Ground/Across Open Contacts) kV 185
Rated Short-Circuit Breaking Current kA 25 / 31.5
Rated Short-Circuit Closing Current (Peak) kA 63 / 80
Rated Peak Withstand Current kA 63 / 80
4s Short-Time Withstand Current kA 25 / 31.5
Rated Operating Sequence   Open-0.1s-Close Open-3s-Close Open-6s-Close Open-60s Recover
Rated Short-Circuit Current Breaking Times Times 30
Mechanical Lifespan Times 10,000
Control Voltage of Mechanism V AC/DC 220
Secondary Circuit 1-Minute Power Frequency Withstand Voltage kV 2