Eco-Friendly Gas-Insulated Ring Main Unit HXGN(H)□-12
EXW
$3,825.39
China
No. 439, Yizhi Road, Zone A, Xiaolan Economic and Technological Development Zone, Nanchang County, Nanchang City, Jiangxi Province
0791-88556630
Online Contact
Favorite
Product Introduction

Overview:

The HXGN(H)□-12 eco-friendly gas-insulated ring main unit is a smart cloud device made from environmentally friendly materials, offering an economical price and convenient operation. All conductive parts of the switchgear are installed within a sealed stainless steel gas tank. The gas tank is primarily insulated with dry air and thermoplastic materials. The main switch utilizes vacuum arc extinguishing, and the isolation switch features a three-position structure. Adjacent cabinets are connected via solid insulated busbars. The secondary circuit employs integrated control technology and supports data transmission functions. When the equipment is installed and powered on-site, it sends an initial signal to the central station for a first handshake, allowing the central station to acquire the equipment's health status, coordinate position, operating environment, and operational parameters. This enables maintenance personnel to monitor the equipment's operational status promptly.

Normal Operating Conditions:

  • Maximum temperature: +45°C;
  • Minimum temperature: -25°C;
  • Maximum temperature (24-hour average): +35°C;
  • Maximum average relative humidity (24 hours): ≤95%;
  • Altitude: ≤1500 meters;
  • Seismic capability: 8 degrees;
  • Protection level: Sealed live parts IP67, switchgear housing IP4X;
  • The surrounding air should not be significantly polluted by corrosive or flammable gases, water vapor, etc.;
  • Suitable for locations free from frequent severe vibrations. The design for harsh conditions meets various requirements;
  • For use in conditions exceeding the normal environmental conditions specified in GB/T3906, users should consult with our company.
Technical Specifications

 

Item Unit Parameter
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Insulation Level    
1-Minute Power Frequency Withstand Voltage (to Ground, Between Phases) kV 42
Isolation Distance kV 48
Lightning Impulse Withstand Voltage (Peak) (to Ground, Between Phases) kV 75
Isolation Distance kV 85
Auxiliary/Control Circuit 1-Minute Power Frequency Withstand Voltage (to Ground) kV 2
Rated Current A 630
Rated Short-Time Withstand Current (RMS) kA 25 (Main Circuit/4s), 21.7 (Ground Connection Circuit/4s)
Rated Peak Withstand Current kA 63 (Main Circuit), 54.5 (Ground Connection Circuit)
Rated Short-Circuit Breaking Current and Times kA/Times 25/30
Rated Short-Circuit Making Current (Peak) kA 63
Rated Cable Charging Breaking Current A 25
Circuit Breaker Rated Operating Sequence   O-0.3s-CO-180s-CO
Mechanical Lifespan Times 10,000 (Circuit Breaker), 3,000 (Isolation Switch)
Protection Level    
Sealed Box   IP67
Switchgear Housing   IP4X
Gas Pressure    
Gas Rated Charging Level (20°C, Gauge Pressure) MPa 0.02
Gas Minimum Functional Level (20°C, Gauge Pressure) MPa 0
Sealing Performance   Annual Leakage Rate ≤ 0.05%