Product Introduction

Overview:

The HXGN15-12 modular AC metal-enclosed ring main unit (referred to as the ring main unit) is a new generation of high-voltage electrical products independently designed and developed by our company, based on the introduction of advanced foreign technology and in accordance with the requirements of rural and urban power grid upgrades in China.

The ring main unit's main switch, operating mechanism, and components utilize the SFL-12/24 type switchgear, produced by leading domestic brands. It offers two modes of operation: manual and electric. The cabinet is assembled using CNC machining and riveting, achieving a protection level of IP3X, with reliable mechanical interlocking and anti-misoperation functions. This product is characterized by its compact size, lightweight, aesthetically pleasing appearance, easy operation, long lifespan, high parameters, pollution-free design, and minimal maintenance requirements.

The HXGN15-12 modular AC metal-enclosed ring main unit is suitable for 50Hz, 12kV power networks, where it is used for receiving and distributing electrical energy.

Technical Specifications

 

Item Unit Parameter
Rated Voltage kV 12
Rated Frequency Hz 50
Rated Current of Main Busbar / Maximum Rated Current of Fuse A 630 / 125
Rated Short-Time Withstand Current of Main Circuit and Ground Circuit kA/S 20 / 3
Rated Peak Withstand Current of Main Circuit and Ground Circuit kA 50
Rated Short-Circuit Making Current of Main Circuit and Ground Circuit kA 50
Full Capacity Load Break Times Times 100
Fuse Breaking Current kA 31.5 / 40
Rated Loop Breaking Current A 630
Rated Transfer Current A 1600
Mechanical Lifespan Times 2000
1-Minute Power Frequency Withstand Voltage (Peak) (Phase-to-Phase, to Ground / Across Isolation Break) kV 42 / 48
Lightning Impulse Withstand Voltage (Peak) (Phase-to-Phase, to Ground / Across Isolation Break) kV 75 / 85
Secondary Circuit 1-Minute Power Frequency Withstand Voltage kV 2
Protection Level   IP3X

Dimensions:

Item Unit Parameter
Width of Circuit Breaker Cabinet mm 750
Width of Other Cabinets mm 375 / 500
Height mm 1600 / 1850
Depth mm 980 / 900
Relay Box Height mm 450