0.6/1(1.2)kV cross-linked polyethylene insulated power cable
Negotiable
China
No. 17, Shiyan Avenue, Yufengshan Town, Yubei District, Chongqing City
+86 02361898070
Online Contact
Favorite
Product Introduction

Operating characteristics:

① The maximum long-term allowable operating temperature of the cable conductor is 90℃;

② During a short circuit (lasting no more than 5s), the maximum temperature of the cable conductor shall not exceed 250℃;

③ The ambient temperature during cable installation should not be lower than 0℃. The minimum bending radius of the cable during installation is shown in the table below.

Product Parameters

Product model and name

Model

Name

YJ(L)V

XLPE insulated PVC sheathed power cable

YJ(L)Y

XLPE insulated PE sheathed power cable

YJ(L)V22

XLPE insulated steel tape armored PVC sheathed power cable

YJ(L)V23

XLPE insulated steel tape armored PE sheathed power cable

YJ(L)V32

XLPE insulated fine steel wire armored PVC sheathed power cable

YJ(L)V33

XLPE insulated fine steel wire armored PE sheathed power cable

YJ(L)V62

XLPE insulated non-magnetic metal tape armored PVC sheathed power cable

YJ(L)V72

XLPE insulated non-magnetic wire armored PVC sheathed power cable

WDZ-YJY

XLPE insulated low-smoke halogen-free flame retardant polyolefin sheathed power cable

WDZ-YJY23

XLPE insulated steel tape armored halogen-free low smoke flame retardant polyolefin sheathed power cable

Note:

“① PVC sheathed power cables in the above models, the company can also produce flame retardant, fire-resistant and termite-proof power cables. Add “ZA-”, “ZB-” or “ZC-” before the above models for flame-retardant power cables; add “N-” before the above models for fire-resistant power cables; add “-FY” after the above models for termite-proof power cables”.”

“② According to user needs, our company can also produce the above various specifications of 1kV XLPE insulated low-smoke low-halogen flame-retardant sheathed power cables and low-smoke halogen-free flame-retardant polyolefin sheathed power cables, as well as various fire-resistant cables. "

Cable Installation Minimum Bending Radius Table

Project

Single core cable

Multi-core cable

No Armored

Armored

No Armored

Armored

Minimum bending radius of cable at installation

20 D

15 D

15 D

12 D

Minimum bending radius of the cable near the connection box and the terminal (but the bending should be carefully controlled, such as using a molded guide plate)

15 D

12 D

12 D

10 D

Note: D is the outer diameter of the cable.