Product Introduction

The GIS terminal operates in a fully enclosed environment, unaffected by atmospheric conditions and pollution. Its size is much smaller than outdoor terminals. The external insulation uses an epoxy resin bushing, and it is installed inside the gas-insulated switchgear (GIS), with sulfur hexafluoride gas serving as the external insulation for the gas-insulated cable terminal.

The 110kV GIS terminal is suitable for 240mm²-1600mm².

The 220kV GIS terminal is suitable for 400mm²-2500mm².

Product Parameters

Product Parameters

Project

Technical parameters

110kV GIS Terminal

220kV GIS terminal

Rated voltage and frequency

64/110kV, 50Hz

127/220kV, 50Hz

Maximum operating voltage

126kV

252kV

Ambient temperature

-40 ℃-+50 ℃

-40 ℃-+50 ℃

Maximum conductor temperature during normal operation

90 ℃

90 ℃

Maximum conductor operating temperature at short circuit

250 ℃

250 ℃

Applicable cable cross-sectional area

240mm ²-1600mm ²

300mm ²-2500mm ²

Partial discharge test

96kV, no detectable discharge

190kV, no detectable discharge

Power frequency voltage test

160kV,60min

318kV,60min

Lightning impulse voltage test

± 550kV, 10 times each, no breakdown, no flashover