The Star Charging eBox-AL261 commercial and industrial energy storage system can be widely used in photovoltaic, wind power, grid-connected, and industrial application scenarios. It can be integrated with other energy management products from Star Charging to build a smart energy microgrid. In the smart energy microgrid, the Star Charging eBox-AL261 commercial and industrial energy storage system professionally provides power storage functions, laying the foundation for emergency power supply during unexpected power outages, peak shaving and valley filling, surplus electricity sales, peak-valley arbitrage, and virtual capacity expansion. The highly integrated cabinet design makes the whole system more space-efficient, with higher energy density, and easier transportation, installation, and operation and maintenance.
eBox-AL261 Commercial and Industrial Energy Storage System
|
System |
|
|
Cell capacity/cell material |
314Ah/LFP Square |
|
DC operating voltage range |
728 ~ 936Vdc |
|
Rated voltage of battery system |
832Vdc |
|
Battery system rated capacity |
261kWh |
|
Battery system available power |
248kWh(95%DOD) |
|
Charge-discharge rate |
≤ 0.5p |
|
Whole cabinet size (w×h×d) |
990 × 2300 (without lifting ring) x1350mm |
|
Net weight (including battery pack) |
≈ 2700kg |
|
Protection level |
IP54 |
|
Operating temperature range |
-20 ℃ +55 ℃ |
|
Anti-corrosion and weather resistance of Cabinet body |
C4/C5 optional based on station environment |
|
Battery temperature control mode |
Liquid cooling |
|
AC side |
|
|
Rated AC voltage |
380V(3W+N+PE) |
|
Rated power |
130kW |
|
Maximum power |
143kW |
|
AC side |
- |
|
Fire Fighting |
|
|
Fire extinguishing agent |
Default perfluorohexanone + water (double fire extinguishing) |
|
Fire detection |
Temperature monitoring, combustible gas monitoring, smoke monitoring |
|
Fire prevention |
Active monitoring and active emission of combustible gas |
|
Explosion-proof capability |
Electric core level pressure relief, PACK level pressure relief, cabinet level pressure relief |
|
Fire form |
Aerosol + PACK immersion + system Cabinet immersion + explosion-proof |
|
Protection |
|
|
Protection function |
Over-under-voltage, over-under-frequency, over-current, over-power, over-temperature, short circuit, anti-reverse connection |
|
Detection function |
Insulation impedance detection |
|
Design Criteria |
|
|
Safety regulations |
GB/T36276-2018, GB/T36276-2023 |
|
Grid connected |
GB/T34120 |