The Star Charging eBox-232 commercial and industrial energy storage system can be widely used in photovoltaic, wind power, grid-connected, and industrial application scenarios. It can be integrated with other energy management products from Star Charging to build a smart energy microgrid. In the smart energy microgrid, the Star Charging eBox-232 commercial and industrial energy storage system professionally provides power storage functions, laying the foundation for emergency power supply during unexpected power outages, peak shaving and valley filling, surplus electricity sales, peak-valley arbitrage, and virtual capacity expansion. The highly integrated cabinet design makes the whole system more space-efficient, with higher energy density, and easier transportation, installation, and operation and maintenance.

Product Specifications

System

Cell capacity/cell material

302Ah/LFP Square

DC operating voltage range

720V ≈ 852V

Rated voltage of battery system

768v

Battery system rated capacity

232kWh

Battery system available power

215kWh(93%DOD)

Charge-discharge rate

≤ 0.47p

Whole cabinet size (width x height x depth)

1,257±5mm×2,200±5mmx1,438±5mm

Net weight (including battery pack)

32557±20kg

Protection level

IP54

Operating temperature range

0 ℃ ~ +45 ℃

Maximum operating temperature

-20 ℃ ~ +55 ℃

Battery temperature control mode

Industrial grade temperature control air conditioning

Fire protection system

Sevoflurane direct fire detection tube fire extinguishing device

PCS specifications

Rated output power

100kVA

Maximum output power (10min)

110kW

Rated grid voltage

380Vac, 3W⁴NHPE

Output voltage frequency

50Hz

Total harmonic distortion of grid-connected current (iTHD)

<3% (rated power)

Protection

Protection function inspection

Over-under-voltage, over-under-frequency, over-current, over-power, over-temperature, short circuit, anti-reverse connection

Measuring function

Insulation impedance detection

Design Criteria

Safety regulations

EC62477, EC62619, EC63056

Grid connected

GB/T34120

EMC

IEC61000-6-2, EC61000-6-4