S13 three-dimensional triangular wound core transformer
Negotiable
China
Second floor, Jiutan Village, Xiuquan Street, Huadu District, Guangzhou, Guangdong, China
+86 15876591363
Online Contact
Favorite
Product Introduction

Product introduction:

The three-dimensional triangular wound core transformer breaks through the traditional planar structure and adopts a three-phase symmetrical three-dimensional structure. The three-phase core magnetic circuit of the product is completely symmetrical, the reluctance is greatly reduced, and the excitation current and no-load loss are significantly reduced. It is a kind of high-efficiency and energy-saving transformer that uses traditional materials but operates with lower noise and a more compact structure. The remarkable effects of this product on energy saving, consumption reduction, material saving and environmental protection are unmatched by products with other structures.

Product Parameters

S13 series 30~2500kVA 10kV series fully sealed distribution transformer

Product Model

Rated voltage

Connection group

No-load loss (W)

Load loss (75℃)
(W)

No-load current (%)

Short circuit impedance (%)

Weight(kg)

Path(mm)

Overall Dimension (mm)
Length x Width x Height

High voltage (kV)

High voltage tapping range

Low voltage (kV)

Weight of the device body

Weight of Insulating Oil

Total weight (kg)

S13-M.RL-30/10

6
6.3
10
10.5
11

±5%
or
±2x2.5%

0.4

Dyn11
or
Yyn0

80

630/600

0.5

4

230

87

345

400

748x765x920

S13-M.RL-50/10

100

910/870

0.5

268

110

440

400

810x735x982

S13-M.RL-63/10

110

1090/1040

0.46

300

112

490

400

820x755x990

S13-M.RL-80/10

130

1310/1250

0.44

360

115

540

400

845x825x1020

S13-M.RL-100/10

150

1580/1500

0.42

420

138

640

550

880x860x1070

S13-M.RL-125/10

170

1890/1800

0.4

470

158

705

550

910x850x1090

S13-M.RL-160/10

200

2310/2200

0.38

570

175

820

550

940x895x1160

S13-M.RL-200/10

240

2730/2600

0.36

620

188

915

550

970x905x1180

S13-M.RL-250/10

290

3200/3050

0.34

730

210

1050

550

1305x800x1220

S13-M.RL-315/10

340

3830/3650

0.32

810

240

1395

550

1320x865x1290

S13-M.RL-400/10

410

4520/4300

0.32

1080

280

1565

660

1410x880x1358

S13-M.RL-500/10

480

5410/5150

0.3

1260

325

1850

660

1520x920x1485

S13-M.RL-630/10

570

6200

0.3

4.5

1480

410

2180

820

1572x985x1510

S13-M.RL-800/10

700

7500

0.28

1640

425

2480

820

1620x1085x1545

S13-M.RL-1000/10

830

10300

0.26

1780

445

2745

820

1880x1220x1595

S13-M.RL-1250/10

970

12000

0.24

2120

510

3305

820

1850x1275x1685

S13-M.RL-1600/10

1170

14500

0.22

2620

600

3975

820

2050x1310x1765

S13-M.RL-2000/10

1505

18500

0.2

5.5

3000

890

4785

1070

2150x1360x1960

S13-M.RL-2500/10

1785

21500

0.18

3425

1150

5625

1070

2350x1680x2120

 

SZ13 200~2500kVA 10kV series on-load voltage regulating transformer

Product Model

Rated voltage

Connection group

No-load loss (W)

Load loss (75℃)
(W)

No-load current (%)

Short circuit impedance (%)

Weight (kg)

Path
(mm)

Overall Dimension (mm) Reference Length x Width x Height

High voltage (kV)

High voltage tapping range

Low voltage (kV)

Weight of the device body

Weight of Insulating Oil

Total; weight (Kg)

SZ13-200/10

6.3
10
10.5
11

±4 x 2.5%

0.4

Dn11y
or
Yyno

240

2900

0.36

4

620

238

1015

550

1470x905x1180

SZ13-250/10

290

3420

0.34

730

260

1150

550

1805x85120x20

SZ13-315/10

340

4100

0.32

810

290

1495

550

1820x865x1290

SZ13-400/10

410

4960

0.32

1080

330

1665

660

1910x880x1358

SZ13-500/10

480

5900

0.3

1260

375

1950

660

2020x9208x145

SZ13-630/10

570

7200

0.3

4.5

1480

450

2280

820

2072x985x1510

SZ13-800/10

700

8900

0.28

1640

475

2580

820

2120x1085x1545

SZ13-1000/10

830

10400

0.26

1780

495

2845

820

2380x1220x1595

SZ13-1250/10

970

12400

0.24

2120

560

3405

820

2350x1275x1685

SZ13-1600/10

1170

14800

0.22

2620

650

4075

820

2550x1310x1765

SZ13-2000/10

1505

18500

0.22

5.5

3000

940

4885

1070

2650x1360x1960

SZ13-2500/10

1785

21500

0.18

3425

1200

5725

1070

2850x1680x2120

Note: The dimensions and weights in the table are for reference only. The actual design shall prevail.

Note: The load loss values above the slash in the table are applicable to Dyn11 or Yzn11 connection groups, and the load loss values below the slash are applicable to Yyn0 connection groups.

The dimensions and weights in the table are for reference only. The actual design shall prevail.