The GCK low-voltage withdrawable switchgear is widely used in power plants, substations, industrial enterprises, and high-rise buildings’ power distribution centers (PC) and motor control centers (MCC). It serves as a low-voltage complete distribution device for power distribution, motor centralized control, and reactive power compensation in power generation and supply systems with an AC frequency of 50-60Hz, a rated working voltage of 660V or below, and a rated current of 4000A or below.
Technical Parameters:
Rated frequency: 50Hz
Horizontal busbar: 1250~6000A
Rated current: 6300A
Rated insulation voltage: AC 660V, AC 1000V
Rated working voltage: AC 380V, AC 660V
Rated frequency: 50Hz
Maximum current for feeder circuits: 3150A
Maximum current for drawer circuits: 3150A
Maximum motor control capacity: 320kW
Peak withstand current for horizontal busbar (1s): 63kA, 105kA, 176kA
Short-time withstand current for horizontal busbar (1s): 30kA, 50kA, 80kA, 100kA
Peak withstand current for vertical busbar (1s): 63kA, 105kA
Short-time withstand current for vertical busbar (1s): 30kA, 50kA
Rated power frequency withstand voltage (1min): 2500V
Secondary power frequency withstand voltage (1min): 2500V
Protection level: IP30, IP40
Dimensions (width * depth * height in mm): 600 (800, 1000) * 800 (1000) * 2200