Gas Alarm Controller SD8001 Series
Negotiable
China
China (Sichuan) Pilot Free Trade Zone Room 502, Area 7, Haolang Technology Park, 2666 Konggang 4th Road, Southwest Airport Economic Development Zone, Shuangliu District, Chengdu, Sichuan Province
+86 028-81511655
Online Contact
Favorite
Product Introduction

Main performance and features:  

① S-BUS bus system signal transmission (+24V, GND, S+, S-)  

② LED display  

③ Resistant to RF/EMI interference  

④ Two-level alarms: low-limit alarm and high-limit alarm  

⑤ Automatic fault monitoring  

When any of the following conditions occur, the controller can emit a distinct sound and light fault signal that is significantly different from the gas alarm signal:  

When there is a short circuit or disconnection fault in the connection line between the controller and the detector;  

When there is a detector fault;  

When there is a main power supply/backup power supply fault.  

⑥ Linked output, with configurable linkage output methods and logic  

Two-way linkage output can control two external devices (fans or solenoid valves).  

⑦ Power conversion function  

Main and backup power supply with seamless switching between them, and indicators for the working status of the main and backup power supplies.  

⑧ Ability to save 999 alarm records and 999 fault records separately  

Query the last 999 alarm and fault records, with information retained even in power failure.  

⑨ Battery protection function  

When only the backup power is working and the battery voltage is low, the system automatically shuts down to protect the battery.  

⑩ TTL/MODBUS host communication interface for communication with the host computer.

Product Parameters

Technical indicators

Working voltage:

AC160V-AC265V(50Hz ± 1%)

System capacity:

SD8001A ≤ 4 points SD8001B ≤ 8 points

Testing unit:

%LEL

Power consumption:

≤ 10W (excluding supporting equipment)

Load capacity:

24V maximum output current ≤ 0.5A(4 points)/≤ 1A(8 points)

Use environment:

Temperature -10 ℃ ~ 55 ℃, relative humidity ≤ 93% RH

Alarm mode:

Sound and light alarm

Indication error:

±3%FS

Display mode:

LED

Signal transmission:

S-BUS bus

Signal transmission distance:

≤ 1500m

Overall weight:

About 2.3kg

Overall dimensions:

300 × 210 × 70mm

Installation method:

Wall-mounted

Upper computer:

1 Host computer communication interface (TTL/5V, standard MODBUS Protocol)

Adapter detector:

Hilde industrial and commercial point-type combustible gas detectors (except free-standing detectors)