Main Performance and Features:
① Branch signal transmission (4-20mA);
② 8 channels, each channel works independently;
③ LCD display, wall-mounted installation;
④ Two-level alarms: low-limit alarm, high-limit alarm;
⑤ Automatic fault monitoring:
When one of the following conditions occurs, the controller can emit fault signals that are significantly different from the gas alarm signal:
- Short circuit or disconnection between the controller and the detector wiring;
- Detector malfunction;
- Controller main power or backup power failure;
⑥ Linkage output, linkage output mode and logic can be set:
Each channel has 2 linkage outputs, which can control 2 external devices (fans or solenoid valves);
⑦ Power conversion function:
Each channel has independent main and backup power supply, and can switch seamlessly between main and backup power sources, with status indication of both power supplies;
⑧ Can store 999 alarm records and 999 fault records:
Recent 999 alarm and 999 fault records can be queried, and information is not lost during power off;
⑨ Battery protection function:
When only backup power is in use and the battery voltage is low, the system will automatically shut down to protect the battery;
⑩ Equipped with RS485 bus interface, enabling communication with the host computer.