Gas Alarm Controller SD8006 Series
Negotiable
China
China (Sichuan) Pilot Free Trade Zone Room 502, Area 7, Haolang Technology Park, 2666 Konggang 4th Road, Southwest Airport Economic Development Zone, Shuangliu District, Chengdu, Sichuan Province
+86 028-81511655
Online Contact
Favorite
Product Introduction

Main performance and features:  

① Bus signal transmission (+24V, GND, S+, S-)  

② 4-way bus interface, capable of connecting 256 devices  

③ 7-inch TFT color LCD display  

④ Chinese input functionality  

⑤ Resistant to RF/EMI interference  

⑥ Two-level alarms: low-limit alarm and high-limit alarm  

⑦ Automatic fault monitoring  

When any of the following conditions occur, the controller emits a distinct sound and light fault signal:  

When there is a short circuit or disconnection fault in the connection line between the controller and the detector;  

When there is a detector fault;  

When there is a main power supply or backup power supply fault.  

⑧ Linked output with configurable linkage output methods and logic  

Four-way linkage output can control four external devices (fans or solenoid valves).  

⑨ Ability to save 999 alarm records and 999 fault records separately  

Query the last 999 alarm and fault records, with information retained even in power failure.  

⑩ Power conversion function  

Main and backup power supply with seamless switching and indicators for the working status of each power supply.  

⑪ RS485 bus interface for communication with the host computer.

Product Parameters

Technical indicators

Working voltage:

AC220V (50Hz ± 1%)

System capacity:

256

Testing unit:

%LEL/%VOL/10-6 (PPM)

Power consumption:

≤ 20W (excluding supporting equipment)

Installation method:

Wall-mounted

Overall weight:

About 12kg

Display mode:

7 inch TFT color screen

Signal transmission:

S-BUS bus

Transmission distance:

≤ 1500m

Alarm mode:

Sound and light alarm

Overall dimensions:

500 × 350 × 100mm

Usage environment:

Temperature 0 ℃ ~ 55 ℃, relative humidity ≤ 93% RH

Indication error:

±5%FS

Output:

Capacity 10A/DC24V or 10A/AC220V,

RS485 bus interface (standard MODBUS protocol)

Adapter detector:

Shield industrial and commercial point type combustible gas detector